3RW5115-1XC14-0S — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)11 W
Rated motor power at 230 V (40 °C)5.5 W
Rated operational current at 40 °C43.3 A
Rated operational current at 50 °C39 A
Rated operational current at 60 °C33.9 A
Rated insulation voltage480 V
Minimum settable current (% of Ie)15 %; Relative to smallest settable Ie
Power loss during startup (50 °C)295 W
3RW5115-1XC14-0S — Control & Connection
ParameterValue
Control supply voltage typeAC
Main circuit terminal typebox terminal
Control circuit wire range, solid1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
Control circuit wire range, finely stranded (with ferrule)1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
Analog outputYes; 4 ... 20 mA (default) / 0 ... 10 V (parameterizable with High Feature HMI)
Auxiliary contact rated current, AC-15 at 250 V3 A
Control supply voltage tolerance, AC 50 Hz (max.)10 %
Control supply voltage tolerance, AC 50 Hz (min.)-15 %
Control supply voltage tolerance, AC 60 Hz (max.)10 %
Control supply voltage tolerance, AC 60 Hz (min.)-15 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
Operating voltage tolerance, inside-delta (max.)10 %
Operating voltage tolerance, inside-delta (min.)-15 %
3RW5115-1XC14-0S — Protection & Features
ParameterValue
Motor overload protectionYes
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2
3RW5115-1XC14-0S — Mechanical
ParameterValue
Height321 mm
Width185 mm
Depth203 mm
Weight5.2 kg
Mounting position+/- 10° rotation possible and can be tilted forward or backward on vertical mounting surface
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm
3RW5115-1XC14-0S — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude5 000 mm; Derating as of 1000 m, see catalog
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)
3RW5115-1XC14-0S — Specifications
ParameterValue
Trip ClassCLASS 10A (default) / 10E / 20E; acc. to IEC 60947-4-2
Number Of Controlled Phases3
Utilization category according to IEC 60947-4-2AC-53b
Product Feature Integrated Bypass Contact SystemNo
Start-Up Ramp Time Of Soft Starter0 ... 20 s
Ramp-Down Time Of Soft Starter0 ... 20 s
3RW5115-1XC14-0S — Electrical
ParameterValue
Current Limiting Value [%] Adjustable130 ... 700 %
Starting Voltage [%]30 ... 100 %
Stopping Voltage [%]50 %; non-adjustable

Product details

Soft Starter for Motor Starting Duty

The Siemens 3RW5115-1XC14-0S is a SIRIUS soft starter designed for three-phase induction motors, with a rated operational voltage of 200 to 480 V AC (50/60 Hz). Its default trip class is CLASS 10A per IEC 60947-4-2, with selectable 10E and 20E classes — meaning it protects the motor during starts against the standard thermal overload curve for that class. The minimum load setting is 15% of the smallest settable Ie, which covers lightly loaded motors. The unit supports PROFIBUS, Modbus RTU, and PROFINET standard fieldbuses, plus an analog output configurable as 4-20 mA or 0-10 V (requires High Feature HMI for voltage mode). Starting modes include voltage ramp (adjustable 30-100% starting voltage), soft torque, and soft stop (ramp-down). Inside-delta circuit wiring is supported, which reduces the rated current through the soft starter for larger motors. The unit also features auto-reset, remote reset (by cycling control supply), an error logbook, and firmware update capability.

Fastening is by screw fixing. Dimensions are 321 mm height, 185 mm width, and 203 mm depth. Minimum clearances around the unit: 100 mm upwards, 10 mm forwards, 0 mm backwards, 75 mm downwards, and 5 mm at the sides. The mounting position allows ±10° rotation and can be tilted forward or backward on a vertical surface. Vibration resistance is 15 mm at 6 Hz, 2g to 500 Hz; shock resistance is 15 g / 11 ms (12 g / 11 ms with potential contact lifting).

Control circuit connections use screw-type terminals. The unit is supplied with a standard HMI and supports a High Feature HMI for parameterization of analog output voltage mode and other advanced settings.

Frequently asked questions

Does the 3RW5115-1XC14-0S have a built-in bypass?

The evidence does not list a built-in bypass contactor. The unit supports inside-delta circuit wiring and soft stop ramp-down, but an external bypass contactor is typically added for continuous running applications to reduce heat dissipation.

What is the trip class of 3RW5115-1XC14-0S?

Default trip class is CLASS 10A per IEC 60947-4-2, with selectable 10E and 20E classes.

Is 3RW5115-1XC14-0S suitable for 480V?

Yes, the rated voltage range of 200 to 480 V AC includes 480 V systems.