Skip to main content
Siemens 3RW5116-1XC14 — Soft Starters

Siemens 3RW5116-1XC14 SIRIUS Soft Starter, 200-480 V

MPN3RW5116-1XC14

Siemens SIRIUS 3RW5116-1XC14 soft starter, 200-480 V, trip class 10A, PROFIBUS and PROFINET, screw fixing.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RW5116-1XC14 — Identification
ParameterValue
Product brand nameSIRIUS
3RW5116-1XC14 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)15 kW
Rated motor power at 230 V (40 °C)7.5 kW
Rated operational current at 40 °C55.4 A
Rated operational current at 50 °C49 A
Rated operational current at 60 °C45 A
Minimum settable current (% of Ie)15 %; Relative to smallest settable Ie
Power loss during startup (50 °C)323 W
3RW5116-1XC14 — Control & Connection
ParameterValue
Control supply voltage typeAC
Main circuit terminal typebox terminal
Control circuit wire range, solid1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
Control circuit wire range, finely stranded (with ferrule)1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
Analog outputYes; 4 ... 20 mA (default) / 0 ... 10 V (parameterizable with High Feature HMI)
Auxiliary contact rated current, AC-15 at 250 V3 A
Control supply voltage tolerance, AC 50 Hz (max.)10 %
Control supply voltage tolerance, AC 50 Hz (min.)-15 %
Control supply voltage tolerance, AC 60 Hz (max.)10 %
Control supply voltage tolerance, AC 60 Hz (min.)-15 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
Operating voltage tolerance, inside-delta (max.)10 %
Operating voltage tolerance, inside-delta (min.)-15 %
3RW5116-1XC14 — Protection & Features
ParameterValue
Motor overload protectionYes
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2
3RW5116-1XC14 — Mechanical
ParameterValue
Height321 mm
Width185 mm
Depth203 mm
Weight5.2 kg
Mounting position+/- 10° rotation possible and can be tilted forward or backward on vertical mounting surface
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm
3RW5116-1XC14 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude5 000 m; Derating as of 1000 m, see catalog
3RW5116-1XC14 — Specifications
ParameterValue
Trip ClassCLASS 10A (default) / 10E / 20E; acc. to IEC 60947-4-2
Number Of Controlled Phases3
Product Feature Integrated Bypass Contact SystemNo
Start-Up Ramp Time Of Soft Starter0 ... 20 s
3RW5116-1XC14 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable130 ... 700 %
Starting Voltage [%]30 ... 100 %
Stopping Voltage [%]50 ... 50 %

Product details

The 3RW5116-1XC14 is a SIRIUS soft starter sized for three-phase induction motors on 200-480 VAC lines. The trip class defaults to CLASS 10A per IEC 60947-4-2, meaning it clears a locked-rotor condition within 10 seconds at 7x FLA — standard for most pump, fan, and conveyor starts. You can parameterize it to 10E or 20E if the application needs a longer acceleration ramp (high-inertia loads like a centrifuge or a long belt). The minimum settable motor current is 14 A, so it covers the lower end of the medium-horsepower range without over-sizing the bypass. The control voltage accepts 110-250 V at both 50 and 60 Hz, which keeps the control transformer common across global panels. Communication comes with PROFIBUS and PROFINET onboard — no option card needed for either fieldbus. The analog output defaults to 4-20 mA but can be switched to 0-10 V through the HMI module, giving the DCS a motor-current or ramp-progress signal without a separate transducer.

Mounts via screw fixing on a vertical surface; the enclosure allows +/-10° rotation and forward/backward tilt. Clearance requirements: 100 mm above, 75 mm below, 10 mm forward, 5 mm at the sides, and 0 mm backward — the back can sit flat against the panel backplate. That 100 mm upward gap is critical for heat plume rise; crowding it forces derating. The protection class is IP00 out of the box — IP20 is achievable with the optional terminal covers (3RW5980-0HS00) for vertical touch protection. In a pulp mill switchroom that hits 45 °C in summer, you need to either up-size the starter or add forced ventilation. Shock resistance is 15 g / 11 ms; vibration tolerance is 15 mm at 6 Hz and 2 g up to 500 Hz, which handles most motor-starter cubicle vibration without contact chatter.

Frequently asked questions

Where can I buy a Siemens 3RW5116-1XC14 soft starter?

This part is sourced to order against an RFQ through independent distribution. Submit a request for current pricing and availability — lead time and stock are confirmed at quote time.

Does the 3RW5116-1XC14 require an external bypass contactor?

The soft starter supports an inside-delta circuit configuration, which reduces line current during bypass. An external bypass contactor is not mandatory — the unit can run in continuous-duty mode — but adding one extends starter life by taking the thyristors out of the circuit after the motor reaches full speed.

What is 3RW5116-1XC14's listed depth?

The depth is 203 mm, with a width of 185 mm and a height of 321 mm.

MPN
3RW5116-1XC14