Skip to main content
Siemens 3RW5213-1TC04

Siemens 3RW5213-1TC04 SIRIUS Soft Starter, 200-480 V

MPN 3RW5213-1TC04
Active

Siemens SIRIUS 3RW5213-1TC04 soft starter, rated 200-480 V, minimum current 5.5 A, trip class 10A (default) / 10E / 20E per IEC 60947-4-2, with PROFIBUS, Modbus RTU, Modbus TCP, and EtherNet/IP.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RW5213-1TC04 specifications
ParameterValue
Mountingscrew fixing
Depth152 mm
Width170 mm
Height275 mm
Trip classCLASS 10 A (default) / 10E / 20E; acc. to IEC 60947-4-2
Service factor1
Digital output version2 normally-open contacts (NO) / 1 changeover contact (CO)

Product details

The Siemens 3RW5213-1TC04 is a SIRIUS hybrid soft starter designed for three-phase induction motors on 200-480 V supplies. Its trip class — CLASS 10A by default, with selectable 10E or 20E per IEC 60947-4-2 — means it protects motors during start-up by limiting thermal stress, and the 10A setting clears a stalled rotor fast enough for most pump and fan loads without nuisance tripping. The minimum settable current is 5.5 A, so it covers smaller motors down to about 2.2 kW on a 400 V line.

Screw-fixing mount, 275 mm tall by 170 mm wide by 152 mm deep. Clearance callouts: 100 mm above, 75 mm below, 10 mm in front, 5 mm at the sides, and zero behind — so it sits tight to the backplane, but you need headroom for cable entry and airflow. The mounting surface can tilt up to ±10° from vertical. Terminals accept two conductors per pole: 1.0–2.5 mm² and 2.5–10 mm². That covers standard motor cables up to 6 mm² for a 5.5 A minimum load without needing adapters.

Communications and control

Built-in fieldbus: PROFIBUS, Modbus RTU, Modbus TCP, and EtherNet/IP. No separate communication module needed — one order code covers the main protocols an integrator will encounter. PROFIenergy is supported when used with a PROFINET communication module, and the unit can be remotely reset by cycling the 24 V control supply. Soft Torque and Pump Ramp Down are standard — useful for reducing water hammer in pump starts and avoiding pressure surges on stop. No analog output, but the error logbook is available with an accessory.

Lifecycle and approvals

Marked as current production — no phase-out or NRND flag. CE, UL, and CSA approvals are all present, so it ships into North American and European panels without a certificate chase. Shock rated at 15 g / 11 ms, which is robust for general industrial panels but not extreme for mobile equipment.

MPN
3RW5213-1TC04