3RW5213-1TC15 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS
3RW5213-1TC15 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)5.5 kW
Rated motor power at 230 V (40 °C)3 kW
Rated operational current at 40 °C22.5 A
Rated operational current at 50 °C19.9 A
Rated operational current at 60 °C18.2 A
Rated insulation voltage600 V
Minimum settable current (% of Ie)15 %; Relative to smallest settable Ie
Power loss during startup (50 °C)178 W
3RW5213-1TC15 — Control & Connection
ParameterValue
Control supply voltage typeAC
Main circuit terminal typescrew-type terminals
Control circuit wire range, solid1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
Control circuit wire range, finely stranded (with ferrule)1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
Analog outputNo
Auxiliary contact rated current, AC-15 at 250 V3 A
Auxiliary contact rating (UL)R300-B300
Control supply voltage tolerance, AC 50 Hz (max.)10 %
Control supply voltage tolerance, AC 50 Hz (min.)-15 %
Control supply voltage tolerance, AC 60 Hz (max.)10 %
Control supply voltage tolerance, AC 60 Hz (min.)-15 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
Operating voltage tolerance, inside-delta (max.)10 %
Operating voltage tolerance, inside-delta (min.)-15 %
3RW5213-1TC15 — Protection & Features
ParameterValue
Motor overload protectionYes; Full motor protection (thermistor motor protection and electronic motor overload protection)
Thermistor motor protectionYes; Type A PTC or Klixon / Thermoclick
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2
3RW5213-1TC15 — Mechanical
ParameterValue
Height275 mm
Width170 mm
Depth152 mm
Weight2.1 kg
Mounting position+/- 10° rotation possible and can be tilted forward or backward on vertical mounting surface
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm
3RW5213-1TC15 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude5 000 m; Derating as of 1000 m, see catalog
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)
3RW5213-1TC15 — Specifications
ParameterValue
Trip ClassCLASS 10A (default) / 10E / 20E; acc. to IEC 60947-4-2
Number Of Controlled Phases3
Utilization category according to IEC 60947-4-2AC 53a
Product Feature Integrated Bypass Contact SystemYes
Start-Up Ramp Time Of Soft Starter0 ... 20 s
3RW5213-1TC15 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable130 ... 700 %
Starting Voltage [%]30 ... 100 %
Stopping Voltage [%]50 %; non-adjustable

Product details

Motor starting profile and trip class

The 3RW5213-1TC15 is a Siemens soft starter rated for 200-600 V supply, with a minimum settable current of 5.5 A. Its trip class defaults to CLASS 10A per IEC 60947-4-2, but can be configured to 10E or 20E — meaning you can match the thermal overload curve to the motor's acceleration time: 10A for standard starts under 10 seconds, 20E for longer ramp-ups like conveyors or crushers. The soft torque feature and pump ramp down function are built in — the ramp down reduces pressure surges in pumping systems by extending the deceleration profile, while soft torque limits inrush on high-inertia loads without oversizing the starter.

Fieldbus and control integration

This unit ships with PROFIBUS onboard, plus support for Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET standard — you can drop it into a Siemens S7 environment or a Rockwell plant-floor network without a separate gateway module. PROFIenergy is supported when used with the PROFINET communication module, allowing energy management profiles during idle periods. Firmware updates are field-loadable, and an error logbook is accessible with the optional accessory. Remote reset is handled by cycling the control supply voltage — no physical button press needed for automated restart sequences.

Mounting and environmental limits

The 3RW5213-1TC15 measures 170 mm wide, 275 mm high, and 152 mm deep — screw-fixing mount, with a +/-10° rotation allowance on a vertical surface. Clearance requirements: 100 mm upwards, 75 mm downwards, 10 mm forwards, 5 mm at the sides, 0 mm backwards. That backwards zero means it can sit flush against a backplate, saving panel depth. Shock rated at 15 g / 11 ms, with potential contact lifting noted at 12 g / 11 ms.

Terminal wiring and approvals

Power terminals accept solid wire: 2x (1.0-2.5 mm²) and 2x (2.5-10 mm²) — covers standard motor cable sizes up to 10 mm². UL and CSA approved, CE marked — the compliance documentation covers the major North American and European jurisdictions without extra certification legwork.

MPN