Fieldbus integration and protection profile
The 3RW5213-3AC05 supports PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET standard — it drops into a multi-protocol line without a gateway. PROFIsafe not listed; safety separation handled externally. Trip class is configurable: default CLASS 10A, with 10E and 20E selectable per IEC 60947-4-2.
Sizing and thermal derating
Minimum set current is 5.5 A, with a 15 % minimum load relative to the smallest settable Ie — so the bottom end is about 0.83 A. Ambient derating starts at 40 °C; full rating holds from -25 °C to +40 °C. Above 40 °C, output current must be reduced per the derating curve — critical for panels with high internal heat rise. Mounting position allows ±10° rotation and forward/backward tilt on a vertical surface.
Wiring and panel space
Screw fixing, not DIN rail snap-on — plan for a mounting plate or back panel. Dimensions are 275 mm height, 170 mm width, 152 mm depth. Clearance requirements: 100 mm upwards, 10 mm forwards, 75 mm downwards, 5 mm sideways — the upward gap is the biggest constraint; stack multiple units with at least 100 mm between them for airflow.
Lifecycle and compliance documentation
The part carries shock resistance of 15 g / 11 ms, with potential contact lifting above 12 g / 11 ms — relevant for mobile or mining equipment panels where vibration isolation may be needed.