Skip to main content
Siemens 3RW5213-3TC05 — Soft Starters

Siemens 3RW5213-3TC05 SIRIUS Soft Starter, 200-600 V

MPN3RW5213-3TC05
Active

Siemens SIRIUS 3RW5213-3TC05 soft starter, 200-600 V rated, 5.5 A minimum, Class 10A/10E/20E trip, PROFIBUS/Modbus RTU/TCP/EtherNet/IP/PROFINET, screw fixing, 275 x 170 x 152 mm.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RW5213-3TC05 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS
3RW5213-3TC05 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)5.5 kW
Rated motor power at 230 V (40 °C)3 kW
Rated operational current at 40 °C22.5 A
Rated operational current at 50 °C19.9 A
Rated operational current at 60 °C18.2 A
Rated insulation voltage600 V
Minimum settable current (% of Ie)15 %; Relative to smallest settable Ie
Power loss during startup (50 °C)178 W
3RW5213-3TC05 — Control & Connection
ParameterValue
Control supply voltage typeAC/DC
Rated voltage at 50 Hz24 V
Rated voltage at 60 Hz24 V
Main circuit terminal typescrew-type terminals
Control circuit wire range, solid2x (0.25 ... 1.5 mm²)
Control circuit wire range, finely stranded (with ferrule)2x (0.25 ... 1.5 mm²)
Analog outputNo
Auxiliary contact rated current, AC-15 at 250 V3 A
Auxiliary contact rating (UL)R300-B300
Control supply voltage tolerance, AC 50 Hz (max.)20 %
Control supply voltage tolerance, AC 50 Hz (min.)-20 %
Control supply voltage tolerance, AC 60 Hz (max.)20 %
Control supply voltage tolerance, AC 60 Hz (min.)-20 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
Operating voltage tolerance, inside-delta (max.)10 %
Operating voltage tolerance, inside-delta (min.)-15 %
3RW5213-3TC05 — Protection & Features
ParameterValue
Motor overload protectionYes; Full motor protection (thermistor motor protection and electronic motor overload protection)
Thermistor motor protectionYes; Type A PTC or Klixon / Thermoclick
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2
3RW5213-3TC05 — Mechanical
ParameterValue
Height275 mm
Width170 mm
Depth152 mm
Weight2.1 kg
Mounting position+/- 10° rotation possible and can be tilted forward or backward on vertical mounting surface
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm
3RW5213-3TC05 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude5 000 m; Derating as of 1000 m, see catalog
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)
3RW5213-3TC05 — Specifications
ParameterValue
Trip ClassCLASS 10A (default) / 10E / 20E; acc. to IEC 60947-4-2
Number Of Controlled Phases3
Utilization category according to IEC 60947-4-2AC 53a
Product Feature Integrated Bypass Contact SystemYes
Start-Up Ramp Time Of Soft Starter0 ... 20 s
3RW5213-3TC05 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable130 ... 700 %
Starting Voltage [%]30 ... 100 %
Stopping Voltage [%]50 %; non-adjustable

Product details

SIRIUS soft starter — 200-600 V, Class 10A/10E/20E trip

The Siemens 3RW5213-3TC05 is a SIRIUS hybrid switching device — a soft starter for three-phase induction motors, rated for a supply voltage range of 200 to 600 V and a minimum settable current of 5.5 A. Trip class is selectable between Class 10A (default), 10E, or 20E per IEC 60947-4-2 — this determines the allowable overload duration during start. Class 10A suits standard start times under 10 seconds; Class 20E allows longer acceleration for high-inertia loads like conveyors or centrifuges.

Fieldbus and communication options

Built-in support for PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET — the unit integrates directly into common industrial networks without an external gateway. PROFIenergy is available when used with the PROFINET standard communication module, enabling energy-management data exchange during idle periods. Firmware updates are supported in the field, matching the commissioning engineer's need to align with plant-wide software revisions.

Mounting, wiring, and clearances

Fastened via screw fixing — dimensions 275 mm height, 170 mm width, 152 mm depth. The mounting position allows +/-10° rotation and tilt forward/backward on a vertical surface. Required clearances: 100 mm upwards, 10 mm forwards, 0 mm backwards, 75 mm downwards, 5 mm at the side — these keep airflow and arc-flash separation intact.

CE marked, UL approved, CSA approved — accepted in North American and European installations without additional agency review. Rated operating temperature -25 to +60 °C during operation with derating above 40 °C — the thermal budget matters for panels with multiple drives stacked close. Shock resistance 15 g / 11 ms (12 g / 11 ms with potential contact lifting) — suitable for machine-mounted applications with moderate vibration.

MPN
3RW5213-3TC05