Skip to main content
Siemens 3RW5214-3TC04 — Soft Starters

Siemens 3RW5214-3TC04 SIRIUS Soft Starter, 200-480V, 18A

MPN3RW5214-3TC04
Active

Siemens SIRIUS 3RW5214-3TC04 soft starter, 200-480 VAC, 18 A rated, Class 10A/10E/20E, with PROFIBUS, Modbus RTU/TCP, EtherNet/IP, PROFINET, screw fixing, 275 x 170 x 152 mm.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RW5214-3TC04 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS
3RW5214-3TC04 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)7.5 kW
Rated motor power at 230 V (40 °C)4 kW
Rated operational current at 40 °C31.5 A
Rated operational current at 50 °C28 A
Rated operational current at 60 °C23.9 A
Rated insulation voltage600 V
Minimum settable current (% of Ie)15 %; Relative to smallest settable Ie
Power loss during startup (50 °C)241 W
3RW5214-3TC04 — Control & Connection
ParameterValue
Control supply voltage typeAC/DC
Rated voltage at 50 Hz24 V
Rated voltage at 60 Hz24 V
Main circuit terminal typescrew-type terminals
Control circuit wire range, solid2x (0.25 ... 1.5 mm²)
Control circuit wire range, finely stranded (with ferrule)2x (0.25 ... 1.5 mm²)
Analog outputNo
Auxiliary contact rated current, AC-15 at 250 V3 A
Auxiliary contact rating (UL)R300-B300
Control supply voltage tolerance, AC 50 Hz (max.)20 %
Control supply voltage tolerance, AC 50 Hz (min.)-20 %
Control supply voltage tolerance, AC 60 Hz (max.)20 %
Control supply voltage tolerance, AC 60 Hz (min.)-20 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
Operating voltage tolerance, inside-delta (max.)10 %
Operating voltage tolerance, inside-delta (min.)-15 %
3RW5214-3TC04 — Protection & Features
ParameterValue
Motor overload protectionYes; Full motor protection (thermistor motor protection and electronic motor overload protection)
Thermistor motor protectionYes; Type A PTC or Klixon / Thermoclick
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2
3RW5214-3TC04 — Mechanical
ParameterValue
Height275 mm
Width170 mm
Depth152 mm
Weight2.1 kg
Mounting position+/- 10° rotation possible and can be tilted forward or backward on vertical mounting surface
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm
3RW5214-3TC04 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude5 000 m; Derating as of 1000 m, see catalog
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)
3RW5214-3TC04 — Specifications
ParameterValue
Trip ClassCLASS 10A (default) / 10E / 20E; acc. to IEC 60947-4-2
Number Of Controlled Phases3
Utilization category according to IEC 60947-4-2AC 53a
Product Feature Integrated Bypass Contact SystemYes
Start-Up Ramp Time Of Soft Starter0 ... 20 s
3RW5214-3TC04 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable130 ... 700 %
Starting Voltage [%]30 ... 100 %
Stopping Voltage [%]50 %; non-adjustable

Product details

The Siemens 3RW5214-3TC04 is a SIRIUS soft starter for three-phase induction motors from 7.5 A minimum up to its rated current, on supplies from 200 to 480 VAC. It is part of the current-production SIRIUS family — still active, no end-of-life notice. This is the version with integrated PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET, plus PROFIenergy support when paired with the PROFINET communication module. Control voltage is 24 VDC.

Trip Class and Starting Duty

The soft starter is configurable to Trip Class 10A (default), 10E, or 20E per IEC 60947-4-2. Class 10A is the standard for most motor starts — it allows the starter to carry 7x rated current for about 10 seconds before tripping, matching a standard induction-motor acceleration curve. Class 20E gives more headroom for high-inertia loads like centrifuges or crushers. Minimum load is 15% of the smallest settable Ie.

Fieldbus and Control

Onboard protocols: PROFIBUS DP, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET. No analog output; torque control not supported. Remote reset by cycling 24 VDC control supply.

Screw fixing to a vertical surface; the unit can be tilted ±10° forward or backward. Clearances: 100 mm above, 75 mm below, 10 mm front, 5 mm sides, 0 mm rear. Shock rated to 15 g / 11 ms — tough enough for most industrial panels, but potential contact lifting starts at 12 g / 11 ms.

Termination

Spring-cage terminals accept 2x (1.0 to 2.5 mm²) and 2x (2.5 to 10 mm²) — solid or ferruled stranded. The 10 mm² capacity covers standard motor cables up to about 8 AWG.

Frequently asked questions

Is 3RW5214-3TC04 compatible with PROFIBUS and Modbus?

Yes, it supports PROFIBUS DP, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET — all onboard.

Where can I buy Siemens 3RW5214-3TC04 with fast shipping?

This part is sourced to order; availability and pricing are confirmed at quote time.

MPN
3RW5214-3TC04