Siemens 3RW5215-1AC05 — Soft Starters

Siemens 3RW5215-1AC05 SIRIUS Soft Starter, 11.5 A, 200-600 V

MPN3RW5215-1AC05
Active

Siemens SIRIUS 3RW5215-1AC05 soft starter, 11.5 A minimum, 200-600 V, Class 10A/10E/20E, screw fixing, 275 x 170 x 152 mm.

$617.22Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RW5215-1AC05 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS
3RW5215-1AC05 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)11 kW
Rated motor power at 230 V (40 °C)5.5 kW
Rated operational current at 40 °C43.3 A
Rated operational current at 50 °C39 A
Rated operational current at 60 °C33.9 A
Rated insulation voltage600 V
Minimum settable current (% of Ie)15 %; Relative to smallest settable Ie
Power loss during startup (50 °C)318 W
3RW5215-1AC05 — Control & Connection
ParameterValue
Control supply voltage typeAC/DC
Rated voltage at 50 Hz24 V
Rated voltage at 60 Hz24 V
Main circuit terminal typescrew-type terminals
Control circuit wire range, solid1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
Control circuit wire range, finely stranded (with ferrule)1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
Analog outputYes; 4 ... 20 mA (default) / 0 ... 10 V (parameterizable with High Feature HMI)
Auxiliary contact rated current, AC-15 at 250 V3 A
Auxiliary contact rating (UL)R300-B300
Control supply voltage tolerance, AC 50 Hz (max.)20 %
Control supply voltage tolerance, AC 50 Hz (min.)-20 %
Control supply voltage tolerance, AC 60 Hz (max.)20 %
Control supply voltage tolerance, AC 60 Hz (min.)-20 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
Operating voltage tolerance, inside-delta (max.)10 %
Operating voltage tolerance, inside-delta (min.)-15 %
3RW5215-1AC05 — Protection & Features
ParameterValue
Motor overload protectionYes; Electronic motor overload protection
Thermistor motor protectionNo
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2
3RW5215-1AC05 — Mechanical
ParameterValue
Height275 mm
Width170 mm
Depth152 mm
Weight2.1 kg
Mounting position+/- 10° rotation possible and can be tilted forward or backward on vertical mounting surface
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm
3RW5215-1AC05 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude5 000 m; Derating as of 1000 m, see catalog
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)
3RW5215-1AC05 — Specifications
ParameterValue
Trip ClassCLASS 10A (default) / 10E / 20E; acc. to IEC 60947-4-2
Number Of Controlled Phases3
Utilization category according to IEC 60947-4-2AC 53a
Product Feature Integrated Bypass Contact SystemYes
Start-Up Ramp Time Of Soft Starter0 ... 20 s
3RW5215-1AC05 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable130 ... 700 %
Starting Voltage [%]30 ... 100 %
Stopping Voltage [%]50 %; non-adjustable

Product details

What the trip class means for your motor start

The 3RW5215-1AC05: That's the right call for standard induction motors driving pumps, fans, and compressors — anything that isn't a high-inertia load. If you're starting a centrifuge or a loaded conveyor, you can switch it to CLASS 10E or CLASS 20E to give the motor more time to accelerate. That's a parameter change, not a hardware swap.

Fieldbus options — pick your network

This soft starter supports PROFIBUS, PROFINET standard, Modbus RTU, Modbus TCP, and EtherNet/IP out of the box. That covers the vast majority of plant-floor networks — no separate gateway needed unless you're on DeviceNet or CANopen. PROFIenergy is available when paired with the PROFINET Standard communication module, letting you coordinate energy-saving pauses across a production line during idle periods.

Mounting and clearances for the panel

It mounts with screw fixing, not DIN rail — so budget for four holes in the backplate. The body is 275 mm tall, 170 mm wide, and 152 mm deep, which is a standard footprint for this SIRIUS frame size. Clearance requirements: 100 mm above, 75 mm below, 10 mm in front, 5 mm at the sides, and zero behind. That's tight side-to-side but generous top-to-bottom for cable entry and airflow. The power terminals accept 1.0 to 2.5 mm² on the smaller set and 2.5 to 10 mm² on the larger — fine for the 11.5 A minimum rating. Control wiring is 24 V DC.

Environmental limits and derating

Ambient operating temperature is -25 to +60 °C, but Siemens flags derating above 40 °C. If your panel hits 50 °C, you'll need to reduce the continuous current or add forced ventilation — the spec says 'please observe derating' without giving the curve, so check the manual for the exact factor. Shock resistance is 15 g for 11 ms, dropping to 12 g if you risk contact lifting. That's fine for most industrial floors but marginal near a stamping press or drop forge — mount on vibration isolators if that's your environment.

Lifecycle and sourcing

We source this against your BOM quantity and confirm current pricing and lead time at quote. No stock-holding claim here — it's quoted to order from authorized Siemens distribution.

Frequently asked questions

What compliance documentation does the 3RW5215-1AC05 carry?

It holds UL approval, CSA approval, and CE marking. That covers US, Canadian, and European regulatory acceptance for industrial control equipment.

What voltage range does the 3RW5215-1AC05 work with?

The rated voltage range is 200 to 600 V AC, which covers common global motor voltages from 208 V to 480 V and 600 V Canadian systems.

Can this soft starter handle pump applications with soft stop?

Yes, it includes a pump ramp down function that gradually reduces voltage during stopping, minimizing water hammer in pumping systems.