Skip to main content
Siemens 3RW5215-1TC05 — Soft Starters

Siemens 3RW5215-1TC05 Soft Starter, 11.5 A, 200-600 V

MPN3RW5215-1TC05
Active

Siemens SIRIUS 3RW5215-1TC05 hybrid soft starter, 11.5 A minimum current, 200-600 V rated voltage, Trip Class 10A/10E/20E, PROFIBUS, Modbus RTU/TCP, EtherNet/IP, PROFINET, UL, CSA, CE.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RW5215-1TC05 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS
3RW5215-1TC05 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)11 kW
Rated motor power at 230 V (40 °C)5.5 kW
Rated operational current at 40 °C43.3 A
Rated operational current at 50 °C39 A
Rated operational current at 60 °C33.9 A
Rated insulation voltage600 V
Minimum settable current (% of Ie)15 %; Relative to smallest settable Ie
Power loss during startup (50 °C)318 W
3RW5215-1TC05 — Control & Connection
ParameterValue
Control supply voltage typeAC/DC
Rated voltage at 50 Hz24 V
Rated voltage at 60 Hz24 V
Main circuit terminal typescrew-type terminals
Control circuit wire range, solid1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
Control circuit wire range, finely stranded (with ferrule)1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
Analog outputNo
Auxiliary contact rated current, AC-15 at 250 V3 A
Auxiliary contact rating (UL)R300-B300
Control supply voltage tolerance, AC 50 Hz (max.)20 %
Control supply voltage tolerance, AC 50 Hz (min.)-20 %
Control supply voltage tolerance, AC 60 Hz (max.)20 %
Control supply voltage tolerance, AC 60 Hz (min.)-20 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
Operating voltage tolerance, inside-delta (max.)10 %
Operating voltage tolerance, inside-delta (min.)-15 %
3RW5215-1TC05 — Protection & Features
ParameterValue
Motor overload protectionYes; Full motor protection (thermistor motor protection and electronic motor overload protection)
Thermistor motor protectionYes; Type A PTC or Klixon / Thermoclick
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2
3RW5215-1TC05 — Mechanical
ParameterValue
Height275 mm
Width170 mm
Depth152 mm
Weight2.1 kg
Mounting position+/- 10° rotation possible and can be tilted forward or backward on vertical mounting surface
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm
3RW5215-1TC05 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude5 000 m; Derating as of 1000 m, see catalog
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)
3RW5215-1TC05 — Specifications
ParameterValue
Trip ClassCLASS 10A (default) / 10E / 20E; acc. to IEC 60947-4-2
Number Of Controlled Phases3
Utilization category according to IEC 60947-4-2AC 53a
Product Feature Integrated Bypass Contact SystemYes
Start-Up Ramp Time Of Soft Starter0 ... 20 s
3RW5215-1TC05 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable130 ... 700 %
Starting Voltage [%]30 ... 100 %
Stopping Voltage [%]50 %; non-adjustable

Product details

Motor protection and trip class coordination

The 3RW5215-1TC05: Also configurable to Class 10E or 20E for higher-inertia loads that need a longer acceleration ramp without nuisance tripping. Minimum settable motor current is 11.5 A, which sets the floor for motor full-load amps the unit can protect. Below that, the overload detection may not resolve accurately. Rated voltage covers 200 to 600 V AC, so the same unit works on 208 V北美, 400 V European, and 480/600 V industrial networks without a voltage-range variant.

Fieldbus integration across four protocols

Built-in support for PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET — no separate communication module needed for any of these. PROFIenergy is available when used with the PROFINET standard communication module, enabling energy management during idle phases. The soft starter also carries a remote reset function by cycling the 24 V DC control supply voltage — useful for clearing faults from a PLC or SCADA without a site visit.

Panel mounting and clearance requirements

Clearance requirements: 100 mm upwards, 75 mm downwards, 10 mm forwards, 5 mm at the sides, and 0 mm backwards — so the unit can sit flush against the back panel. Dimensions are 275 mm high, 170 mm wide, and 152 mm deep — a compact footprint for the current range.

Application features for pump and high-inertia loads

Soft torque capability and pump ramp down are both present — the ramp down reduces water hammer on pump stop by gradually reducing voltage instead of cutting power abruptly. This is a standard feature in this SIRIUS generation, not an add-on option. The unit is classified as a hybrid switching device, combining semiconductor switching for the ramp phase with a mechanical bypass contactor for steady-state running — this eliminates semiconductor conduction losses during normal operation.

Compliance and approvals documentation

Carries CE marking for European low-voltage and EMC directives, plus UL and CSA approvals for North American panel acceptance. These are listed on the nameplate; the manufacturer provides the declaration of conformity and UL recognition file on request. Shock resistance is rated at 15 g for 11 ms, with potential contact lifting starting at 12 g / 11 ms — the unit withstands typical industrial vibration and shock without false trips.

Frequently asked questions

How do I get current pricing and availability for 3RW5215-1TC05?

Submit an RFQ for this order code. No stock-holding claim is made here; availability is verified per inquiry.

What is 3RW5215-1TC05's listed depth?

The depth is 152 mm, with a height of 275 mm and width of 170 mm. Clearance above the unit must be 100 mm and below 75 mm for proper ventilation and wiring access.

What compliance documentation does Siemens provide for 3RW5215-1TC05?

CE marking, UL approval, and CSA approval are all listed on the unit. The manufacturer supplies the declaration of conformity and UL/CSA certification documents as part of the standard documentation package.

MPN