Skip to main content
Siemens 3RW5216-1AC14 — Soft Starters

Siemens 3RW5216-1AC14 Soft Starter, 200-480V, CLASS 10A

MPN3RW5216-1AC14
Active

Siemens SIRIUS 3RW5216-1AC14 soft starter, 200-480 V, 14 A minimum, CLASS 10A, with PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET standard communication.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RW5216-1AC14 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS

Power & Motor Rating

3RW5216-1AC14 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)15 kW
Rated motor power at 230 V (40 °C)7.5 kW
Rated operational current at 40 °C55.4 A
Rated operational current at 50 °C49 A
Rated operational current at 60 °C45 A
Rated insulation voltage600 V
Minimum settable current (% of Ie)15 %; Relative to smallest settable Ie
Power loss during startup (50 °C)449 W

Control & Connection

3RW5216-1AC14 — Control & Connection
ParameterValue
Control supply voltage typeAC
Main circuit terminal typescrew-type terminals
Control circuit wire range, solid1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
Control circuit wire range, finely stranded (with ferrule)1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
Analog outputYes; 4 ... 20 mA (default) / 0 ... 10 V (parameterizable with High Feature HMI)
Auxiliary contact rated current, AC-15 at 250 V3 A
Auxiliary contact rating (UL)R300-B300
Control supply voltage tolerance, AC 50 Hz (max.)10 %
Control supply voltage tolerance, AC 50 Hz (min.)-15 %
Control supply voltage tolerance, AC 60 Hz (max.)10 %
Control supply voltage tolerance, AC 60 Hz (min.)-15 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
Operating voltage tolerance, inside-delta (max.)10 %
Operating voltage tolerance, inside-delta (min.)-15 %

Protection & Features

3RW5216-1AC14 — Protection & Features
ParameterValue
Motor overload protectionYes; Electronic motor overload protection
Thermistor motor protectionNo
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2

Mechanical

3RW5216-1AC14 — Mechanical
ParameterValue
Height275 mm
Width170 mm
Depth152 mm
Weight2.3 kg
Mounting positionwith vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm

Environmental

3RW5216-1AC14 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude5 000 m; Derating as of 1000 m, see catalog
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)

Specifications

3RW5216-1AC14 — Specifications
ParameterValue
Trip ClassCLASS 10A (default) / 10E / 20E; acc. to IEC 60947-4-2
Number Of Controlled Phases3
Utilization category according to IEC 60947-4-2AC 53a
Product Feature Integrated Bypass Contact SystemYes
Start-Up Ramp Time Of Soft Starter0 ... 20 s

Electrical

3RW5216-1AC14 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable130 ... 700 %
Starting Voltage [%]30 ... 100 %
Stopping Voltage [%]50 %; non-adjustable

Product details

What this soft starter does on your motor circuit

The Siemens 3RW5216-1AC14 is a hybrid soft starter for three-phase induction motors on 200-480 V supplies. Default trip class is CLASS 10A per IEC 60947-4-2, with minimum settable current of 14 A.

Fieldbus and control wiring

This soft starter ships with onboard PROFIBUS DP, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET standard communication — you don't need a separate gateway module for most networks. The control supply voltage accepts 110-250 V AC at 50 or 60 Hz. For analog feedback, it provides a 4-20 mA output by default, parameterizable to 0-10 V if you pair it with the High Feature HMI accessory. Remote reset is handled by cycling the control supply voltage off then on. The power terminals accept 2x 1.0-2.5 mm² and 2x 2.5-10 mm² solid or stranded conductors.

The unit measures 275 mm high, 170 mm wide, and 152 mm deep, and mounts via screw fixing on a vertical surface. It can be rotated ±90° or tilted ±22.5° front-to-back. Clearance requirements: 100 mm above, 75 mm below, 10 mm forward, 5 mm at the sides, and 0 mm backward — plan your enclosure layout accordingly. Shock resistance is 15 g for 11 ms, with potential contact lifting above 12 g.

Frequently asked questions

Is the Siemens 3RW5216-1AC14 compatible with PROFIBUS?

Yes, the 3RW5216-1AC14 includes onboard PROFIBUS DP communication as standard, along with Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET.

What is the trip class of the 3RW5216-1AC14 and how do I change it?

The default trip class is CLASS 10A per IEC 60947-4-2. You can change it to CLASS 10E or CLASS 20E via the onboard HMI or parameterization tool — no hardware swap required.