Skip to main content
Siemens 3RW5216-3TC05

Siemens 3RW5216-3TC05 SIRIUS Soft Starter, 14 A min

MPN 3RW5216-3TC05
Active

Siemens SIRIUS 3RW5216-3TC05 soft starter, 14 A minimum setting, 200-600 V rated voltage, Class 10A/10E/20E trip class, PROFIBUS/Modbus RTU/Modbus TCP/EtherNet/IP/PROFINET, 275 x 170 x 152 mm (H x W x D).

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RW5216-3TC05 specifications
ParameterValue
Mountingscrew fixing
Depth152 mm
Width170 mm
Height275 mm
Trip classCLASS 10 A (default) / 10E / 20E; acc. to IEC 60947-4-2
Service factor1
Digital output version2 normally-open contacts (NO) / 1 changeover contact (CO)

Product details

What the trip class means for your motor

The 3RW5216-3TC05 ships with a default Trip Class 10A per IEC 60947-4-2, meaning it lets the motor draw locked-rotor current for up to 10 seconds before the soft starter trips — that's the standard for most pump and fan starts where the load accelerates quickly.

Panel fit and mounting constraints

Clearance requirements: 100 mm above, 75 mm below, 10 mm in front, 5 mm at the sides, and zero behind — plan the gland plate and busbar routing accordingly to keep airflow open.

Fieldbus and control integration

This soft starter speaks PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET right out of the box — no extra gateway module needed for most line architectures. It supports PROFIenergy for energy management when paired with the PROFINET communication module, and the firmware is field-upgradable so you can apply later feature releases without swapping hardware.

Ambient temperature and derating

Rated for operation from -25°C to +60°C, but Siemens flags derating above 40°C — if your panel sits in a hot mezzanine or near a furnace, expect to reduce the continuous current rating per the derating curve in the manual. Shock resistance is 15 g for 11 ms, dropping to 12 g if contact lifting is a concern — fine for most industrial floors but worth checking if the starter is mounted on a vibrating compressor skid.

Pump-specific features and minimum load

Includes Pump Ramp Down and Soft Torque profiles — these reduce pressure surges on pipeline restarts and prevent water hammer on stop, which is why this model shows up in water/wastewater BOMs. The minimum settable load is 15% of the smallest Ie setting, and the floor current is 14 A — so it will not regulate down to fractional-horsepower motors; plan your motor FLA against that floor.

Compliance and approvals for export

Carries CE, UL, and CSA marks — covers the main North American and European regulatory jurisdictions without separate certification runs. The service factor is 1.0, meaning no built-in overload margin beyond the nameplate rating — factor that into your coordination study if the driven load has intermittent overload cycles.

MPN