Skip to main content
Siemens 3RW5216-3TC14 — Soft Starters

Siemens 3RW5216-3TC14 Soft Starter, 14 A min, 200-480 V

MPN3RW5216-3TC14
Active

Siemens 3RW5216-3TC14 soft starter, 200-480 V rated, 14 A minimum current, Trip Class 10A/10E/20E, PROFIBUS/Modbus/EtherNet/IP/PROFINET, CE/UL/CSA, active production.

StockContact for availability
Lead time3-5 Days wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RW5216-3TC14 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS

Power & Motor Rating

3RW5216-3TC14 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)15 kW
Rated motor power at 230 V (40 °C)7.5 kW
Rated operational current at 40 °C55.4 A
Rated operational current at 50 °C49 A
Rated operational current at 60 °C45 A
Rated insulation voltage600 V
Minimum settable current (% of Ie)15 %; Relative to smallest settable Ie
Power loss during startup (50 °C)449 W

Control & Connection

3RW5216-3TC14 — Control & Connection
ParameterValue
Control supply voltage typeAC
Main circuit terminal typescrew-type terminals
Control circuit wire range, solid2x (0.25 ... 1.5 mm²)
Control circuit wire range, finely stranded (with ferrule)2x (0.25 ... 1.5 mm²)
Analog outputNo
Auxiliary contact rated current, AC-15 at 250 V3 A
Auxiliary contact rating (UL)R300-B300
Control supply voltage tolerance, AC 50 Hz (max.)10 %
Control supply voltage tolerance, AC 50 Hz (min.)-15 %
Control supply voltage tolerance, AC 60 Hz (max.)10 %
Control supply voltage tolerance, AC 60 Hz (min.)-15 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
Operating voltage tolerance, inside-delta (max.)10 %
Operating voltage tolerance, inside-delta (min.)-15 %

Protection & Features

3RW5216-3TC14 — Protection & Features
ParameterValue
Motor overload protectionYes; Full motor protection (thermistor motor protection and electronic motor overload protection)
Thermistor motor protectionYes; Type A PTC or Klixon / Thermoclick
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2

Mechanical

3RW5216-3TC14 — Mechanical
ParameterValue
Height275 mm
Width170 mm
Depth152 mm
Weight2.3 kg
Mounting positionwith vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm

Environmental

3RW5216-3TC14 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude5 000 m; Derating as of 1000 m, see catalog
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)

Specifications

3RW5216-3TC14 — Specifications
ParameterValue
Trip ClassCLASS 10A (default) / 10E / 20E; acc. to IEC 60947-4-2
Number Of Controlled Phases3
Utilization category according to IEC 60947-4-2AC 53a
Product Feature Integrated Bypass Contact SystemYes
Start-Up Ramp Time Of Soft Starter0 ... 20 s

Electrical

3RW5216-3TC14 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable130 ... 700 %
Starting Voltage [%]30 ... 100 %
Stopping Voltage [%]50 %; non-adjustable

Product details

Motor starting profile and trip class selection

The 3RW5216-3TC14 is a Siemens SIRIUS soft starter rated for 200-480 V supply voltage, with a minimum settable motor current of 14 A. This floor current means it suits smaller motors — typically 5.5-7.5 kW at 400 V — where the full-load current lands above 14 A. Trip class is configurable as CLASS 10A (default), 10E, or 20E per IEC 60947-4-2. CLASS 10A clears an overload in under 10 seconds at 7.2× Ie — standard for most pump and fan starts. In a 50 °C cabinet, expect the continuous current rating to drop — plan the enclosure ventilation or oversize the starter accordingly.

Fieldbus integration and control flexibility

This soft starter supports PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET (with PROFIenergy) — five protocols on one unit. No separate communication module needed for most networks; the onboard interface handles parameter access, start/stop commands, and fault logging. Remote reset is available by cycling the control supply voltage — useful for unattended restart after a fault. Auto-reset is also supported, though use it selectively on safety-critical lines. Pump ramp down is built in — a controlled deceleration profile that reduces water hammer on pump stop, extending valve and pipe life.

Physical mounting and panel layout

Dimensions are 170 mm wide, 275 mm high, 152 mm deep — a standard SIRIUS form factor that fits most 400 mm deep enclosures with room for wiring ducts. Screw fixing to the mounting plate; no DIN rail option. Clearance requirements: 100 mm above, 75 mm below, 10 mm front, 5 mm sides, 0 mm rear. The upward clearance is the tightest — plan the enclosure height so the top vent isn't blocked by a busbar or cable tray. Power terminals accept 1.0-2.5 mm² solid and 2.5-10 mm² stranded — covers standard motor cable sizes up to 10 mm² (roughly 8 AWG).

Sourced through authorized distribution channels. No stock-holding claim; availability verified per request. Compliance documentation includes CE marking, UL approval, and CSA approval — covers EU, US, and Canadian regulatory jurisdictions. No separate RoHS/REACH statement in the record, but the CE mark implies EU compliance.

Frequently asked questions

What is the minimum motor current the 3RW5216-3TC14 can handle?

Minimum settable current is 14 A. This sets the floor for motor full-load current selection — motors drawing below 14 A need a smaller soft starter.

What trip classes are available on the 3RW5216-3TC14?

Configurable as CLASS 10A (default), 10E, or 20E per IEC 60947-4-2. CLASS 10A is standard for normal starts; CLASS 20E suits high-inertia loads with longer acceleration times.

What fieldbus protocols does the 3RW5216-3TC14 support?

Supports PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET (with PROFIenergy) — five protocols onboard without separate modules.

What are the mounting clearances for the 3RW5216-3TC14?

Requires 100 mm clearance above, 75 mm below, 10 mm front, 5 mm sides, 0 mm rear. The upward clearance is critical for heat dissipation.

MPN
3RW5216-3TC14