Siemens SIRIUS 3RW5224-1AC04 soft starter, 200-480 V rated voltage, minimum 20 A setting, CLASS 10A/10E/20E trip class, screw fixing, 306 x 185 x 203 mm.

$787.40Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RW5224-1AC04 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS
3RW5224-1AC04 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)22 kW
Rated motor power at 230 V (40 °C)11 kW
Rated operational current at 40 °C81.4 A
Rated operational current at 50 °C72 A
Rated operational current at 60 °C62.7 A
Rated insulation voltage600 V
Minimum settable current (% of Ie)15 %; Relative to smallest settable Ie
Power loss during startup (50 °C)522 W
3RW5224-1AC04 — Control & Connection
ParameterValue
Control supply voltage typeAC/DC
Rated voltage at 50 Hz24 V
Rated voltage at 60 Hz24 V
Main circuit terminal typebox terminal
Control circuit wire range, solid1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
Control circuit wire range, finely stranded (with ferrule)1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
Analog outputYes; 4 ... 20 mA (default) / 0 ... 10 V (parameterizable with High Feature HMI)
Auxiliary contact rated current, AC-15 at 250 V3 A
Auxiliary contact rating (UL)R300-B300
Control supply voltage tolerance, AC 50 Hz (max.)20 %
Control supply voltage tolerance, AC 50 Hz (min.)-20 %
Control supply voltage tolerance, AC 60 Hz (max.)20 %
Control supply voltage tolerance, AC 60 Hz (min.)-20 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
Operating voltage tolerance, inside-delta (max.)10 %
Operating voltage tolerance, inside-delta (min.)-15 %
3RW5224-1AC04 — Protection & Features
ParameterValue
Motor overload protectionYes; Electronic motor overload protection
Thermistor motor protectionNo
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2
3RW5224-1AC04 — Mechanical
ParameterValue
Height306 mm
Width185 mm
Depth203 mm
Weight5.2 kg
Mounting position+/- 10° rotation possible and can be tilted forward or backward on vertical mounting surface
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm
3RW5224-1AC04 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude5 000 m; Derating as of 1000 m, see catalog
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)
3RW5224-1AC04 — Specifications
ParameterValue
Trip ClassCLASS 10A (default) / 10E / 20E; acc. to IEC 60947-4-2
Number Of Controlled Phases3
Utilization category according to IEC 60947-4-2AC 53a
Product Feature Integrated Bypass Contact SystemYes
Start-Up Ramp Time Of Soft Starter0 ... 20 s
3RW5224-1AC04 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable130 ... 700 %
Starting Voltage [%]30 ... 100 %
Stopping Voltage [%]50 %; non-adjustable

Product details

SIRIUS soft starter for motor starting duty

The Siemens 3RW5224-1AC04 is a SIRIUS-brand hybrid soft starter designed to ramp motors up and down smoothly, reducing inrush current and mechanical stress on pumps, conveyors, and fans. It covers a rated voltage range of 200 to 480 V and sets a minimum starting current of 20 A, with a trip class of CLASS 10A (default), 10E, or 20E per IEC 60947-4-2 — meaning it handles standard and heavy starting duty without nuisance tripping on longer acceleration times.

Fieldbus and control connectivity

This soft starter comes equipped for modern control networks: PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET are all on board, plus PROFIenergy for energy management when used with the PROFINET communication module. Analog output is configurable as 4-20 mA (default) or 0-10 V via the High Feature HMI. Auto-reset and remote reset (by cycling the 24 V control supply) are standard, so a line-down restart can be handled without a panel visit.

Mounting and environmental limits

The unit is screw-fixed (not DIN-rail snap-on) and measures 306 mm high by 185 mm wide by 203 mm deep. Clearance requirements: 100 mm above, 75 mm below, 10 mm forward, 0 mm backward, 5 mm at the sides. Pollution degree 3 per IEC 60947-4-2 means it's rated for industrial environments with conductive dust or moisture.

Frequently asked questions

What is 3RW5224-1AC04's listed depth (203 mm) on this Soft Starters line?

The depth is 203 mm, with width 185 mm and height 306 mm. Mounting is screw-fixed with specified clearances: 100 mm above, 75 mm below, 10 mm forward, 0 mm backward, 5 mm at the sides.