Siemens 3RW5226-1TC15 — Soft Starters

Siemens 3RW5226-1TC15 SIRIUS Soft Starter, 32 A, 200-600 V

MPN3RW5226-1TC15
Active

Siemens SIRIUS 3RW5226-1TC15 soft starter, 32 A minimum, 200-600 V rated voltage, CLASS 10A/10E/20E trip class per IEC 60947-4-2, screw fixing, 306 x 185 x 203 mm.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RW5226-1TC15 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS

Power & Motor Rating

3RW5226-1TC15 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)37 kW
Rated motor power at 230 V (40 °C)22 kW
Rated operational current at 40 °C133 A
Rated operational current at 50 °C118 A
Rated operational current at 60 °C107 A
Rated insulation voltage600 V
Minimum settable current (% of Ie)15 %; Relative to smallest settable Ie
Power loss during startup (50 °C)933 W

Control & Connection

3RW5226-1TC15 — Control & Connection
ParameterValue
Control supply voltage typeAC
Main circuit terminal typebox terminal
Control circuit wire range, solid1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
Control circuit wire range, finely stranded (with ferrule)1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
Analog outputNo
Auxiliary contact rated current, AC-15 at 250 V3 A
Auxiliary contact rating (UL)R300-B300
Control supply voltage tolerance, AC 50 Hz (max.)10 %
Control supply voltage tolerance, AC 50 Hz (min.)-15 %
Control supply voltage tolerance, AC 60 Hz (max.)10 %
Control supply voltage tolerance, AC 60 Hz (min.)-15 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
Operating voltage tolerance, inside-delta (max.)10 %
Operating voltage tolerance, inside-delta (min.)-15 %

Protection & Features

3RW5226-1TC15 — Protection & Features
ParameterValue
Motor overload protectionYes; Full motor protection (thermistor motor protection and electronic motor overload protection)
Thermistor motor protectionYes; Type A PTC or Klixon / Thermoclick
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2

Mechanical

3RW5226-1TC15 — Mechanical
ParameterValue
Height306 mm
Width185 mm
Depth203 mm
Weight5.6 kg
Mounting positionwith vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm

Environmental

3RW5226-1TC15 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude5 000 m; Derating as of 1000 m, see catalog
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)

Specifications

3RW5226-1TC15 — Specifications
ParameterValue
Trip ClassCLASS 10A (default) / 10E / 20E; acc. to IEC 60947-4-2
Number Of Controlled Phases3
Utilization category according to IEC 60947-4-2AC 53a
Product Feature Integrated Bypass Contact SystemYes
Start-Up Ramp Time Of Soft Starter0 ... 20 s

Electrical

3RW5226-1TC15 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable130 ... 700 %
Starting Voltage [%]30 ... 100 %
Stopping Voltage [%]50 %; non-adjustable

Product details

SIRIUS 3RW5226-1TC15 — 32 A soft starter with multi-protocol fieldbus

The Siemens 3RW5226-1TC15 is a SIRIUS hybrid switching device — a soft starter rated for motor starting duty with a minimum settable current of 32 A and a rated voltage range of 200 to 600 V. Trip class is configurable as CLASS 10A (default), 10E, or 20E per IEC 60947-4-2, which governs the allowable motor starting time before the overload protection trips — CLASS 10A suits normal-start loads like pumps and fans, while CLASS 20E handles higher-inertia loads such as centrifuges. On-board fieldbus includes PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET standard with PROFIenergy support, so the starter integrates directly into a PLC-based control architecture without an external gateway.

Mounting, clearance, and thermal derating

Fastened by screw fixing to a vertical mounting surface, the unit can be rotated ±90° or tilted ±22.5° front-to-back, giving panel builders flexibility in orientation within the enclosure. Required clearances: 100 mm upwards, 75 mm downwards, 10 mm forwards, 5 mm at the sides, and 0 mm backwards — these ensure adequate airflow for the internal heatsink and prevent thermal stacking between adjacent devices.

Active production — lifecycle and approvals

Carries UL, CSA, and CE marking — accepted in North American and European installations without additional certification delays. Shock resistance is 15 g / 11 ms, with potential contact lifting above 12 g / 11 ms — relevant for applications on mobile equipment or near vibrating machinery.

MPN