Skip to main content
Siemens 3RW5227-1AC05 — Soft Starters

Siemens 3RW5227-1AC05 SIRIUS Soft Starter, 40.5 A, 200-600 V

MPN3RW5227-1AC05
Active

Siemens SIRIUS 3RW5227-1AC05 soft starter, 40.5 A minimum, 200-600 V, Class 10A/10E/20E, screw fixing, 306 x 185 x 203 mm (HxWxD).

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RW5227-1AC05 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS
3RW5227-1AC05 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)45 kW
Rated motor power at 230 V (40 °C)22 kW
Rated operational current at 40 °C161 A
Rated operational current at 50 °C143 A
Rated operational current at 60 °C131 A
Rated insulation voltage600 V
Minimum settable current (% of Ie)15 %; Relative to smallest settable Ie
Power loss during startup (50 °C)1 077 W
3RW5227-1AC05 — Control & Connection
ParameterValue
Control supply voltage typeAC/DC
Rated voltage at 50 Hz24 V
Rated voltage at 60 Hz24 V
Main circuit terminal typebox terminal
Control circuit wire range, solid1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
Control circuit wire range, finely stranded (with ferrule)1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
Analog outputYes; 4 ... 20 mA (default) / 0 ... 10 V (parameterizable with High Feature HMI)
Auxiliary contact rated current, AC-15 at 250 V3 A
Auxiliary contact rating (UL)R300-B300
Control supply voltage tolerance, AC 50 Hz (max.)20 %
Control supply voltage tolerance, AC 50 Hz (min.)-20 %
Control supply voltage tolerance, AC 60 Hz (max.)20 %
Control supply voltage tolerance, AC 60 Hz (min.)-20 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
Operating voltage tolerance, inside-delta (max.)10 %
Operating voltage tolerance, inside-delta (min.)-15 %
3RW5227-1AC05 — Protection & Features
ParameterValue
Motor overload protectionYes; Electronic motor overload protection
Thermistor motor protectionNo
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2
3RW5227-1AC05 — Mechanical
ParameterValue
Height306 mm
Width185 mm
Depth203 mm
Weight6.9 kg
Mounting positionwith vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm
3RW5227-1AC05 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude5 000 m; Derating as of 1000 m, see catalog
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)
3RW5227-1AC05 — Specifications
ParameterValue
Trip ClassCLASS 10A (default) / 10E / 20E; acc. to IEC 60947-4-2
Number Of Controlled Phases3
Utilization category according to IEC 60947-4-2AC 53a
Product Feature Integrated Bypass Contact SystemYes
Start-Up Ramp Time Of Soft Starter0 ... 20 s
3RW5227-1AC05 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable130 ... 700 %
Starting Voltage [%]30 ... 100 %
Stopping Voltage [%]50 %; non-adjustable

Product details

Panel fit and mounting — 306 x 185 x 203 mm

The 3RW5227-1AC05 measures 306 mm high, 185 mm wide, and 203 mm deep — screw-fixing mount, not DIN rail. Clearance requirements: 100 mm above, 75 mm below, 10 mm forward, 5 mm at the sides, and zero backward clearance needed. That 203 mm depth plus forward clearance means the enclosure depth must be at least 213 mm from the backplane to the door.

Motor starting duty — 40.5 A minimum, trip class options

Rated for a minimum motor current of 40.5 A at 200-600 V AC. The trip class is configurable: default CLASS 10A, with CLASS 10E and CLASS 20E available per IEC 60947-4-2. CLASS 20E gives a longer 20-second ramp for high-inertia loads, reducing thermal stress on the motor during start.

Fieldbus and control — PROFIBUS, PROFINET, Modbus, EtherNet/IP

Built-in support for PROFIBUS, PROFINET standard, Modbus RTU, Modbus TCP, and EtherNet/IP — no separate communication module needed for these protocols. Also supports PROFIenergy for energy management when used with a PROFINET communication module. The analog output is configurable as 4-20 mA or 0-10 V via the High Feature HMI. Remote reset is available by cycling the 24 V DC control supply.

Environmental and approvals — UL, CSA, CE, pollution degree 3

Carries UL, CSA, and CE marking — accepted in North American and European installations. Pollution degree 3 per IEC 60947-4-2 means it tolerates conductive pollution in industrial atmospheres. Operating temperature range -25 to +60 °C, with derating required above 40 °C. Shock resistance 15 g / 11 ms, with potential contact lifting above 12 g.

Frequently asked questions

How do I get current pricing and availability for 3RW5227-1AC05?

Submit an RFQ against your BOM quantity.

What compliance documentation does Siemens provide for 3RW5227-1AC05?

The soft starter carries UL approval, CSA approval, and CE marking. Pollution degree 3 per IEC 60947-4-2. Operating temperature range -25 to +60 °C with derating above 40 °C.

MPN