Skip to main content
Siemens 3RW5234-2TC14

Siemens 3RW5234-2TC14 SIRIUS Soft Starter, 200-480 V

MPN 3RW5234-2TC14
Active

Siemens SIRIUS 3RW5234-2TC14 soft starter, 200-480 V, 53 A minimum, trip class 10A/10E/20E, with PROFIBUS, Modbus RTU/TCP, EtherNet/IP, PROFINET.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RW5234-2TC14 specifications
ParameterValue
Mountingscrew fixing
Depth203 mm
Width185 mm
Height306 mm
Trip classCLASS 10 A (default) / 10E / 20E; acc. to IEC 60947-4-2
Service factor1
Digital output version2 normally-open contacts (NO) / 1 changeover contact (CO)

Product details

Trip Class and Motor Protection

The Siemens 3RW5234-2TC14 SIRIUS soft starter is a hybrid switching device rated for motor starting duty with a trip class of CLASS 10A (default), 10E, or 20E, per IEC 60947-4-2. This means it can handle a 10-second overload at 7x rated current without tripping — typical for standard induction motor starts on pump, fan, or conveyor loads. The 10E and 20E settings extend the thermal memory for longer acceleration times, useful for high-inertia loads like centrifuges or crushers.

Voltage Range and Current Floor

The unit operates on a rated voltage of 200 to 480 V AC. The minimum settable motor current is 53 A.

Fieldbus and Control Integration

This soft starter ships with onboard support for PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET standard. That means it can drop into a controller over PROFINET, an Allen-Bradley CompactLogix over EtherNet/IP, or a legacy Modbus RTU network without an external gateway. The PROFINET interface also supports PROFIenergy, allowing the drive to signal its power state during idle periods for coordinated energy management.

Mounting is screw-fixing on a vertical surface, with the enclosure rotatable ±90° and tiltable ±22.5° front-to-back. Clearance requirements: 100 mm above, 75 mm below, 10 mm forward, 5 mm to the side, and 0 mm backward — so it can sit flush against a back panel.

Environmental and Approvals

Shock resistance is 15 g for 11 ms, with potential contact lifting above 12 g.