The 3RW5234-6AC04: Rated for a minimum load of 53 A, this soft starter is sized for motor applications where the full-load current falls at or above that threshold. Trip class 10A (default) per IEC 60947-4-2. Selectable 10E and 20E classes extend the trip time for higher-inertia loads.
Communication and Control Integration
Built-in PROFIBUS, Modbus RTU, Modbus TCP, and EtherNet/IP support means this unit drops directly into a multi-protocol automation cell without an external gateway. PROFINET standard is also available, with PROFIenergy capability when paired with the PROFINET communication module. The analog output is configurable as 4-20 mA or 0-10 V (via the High Feature HMI), giving the PLC a real-time current or torque signal for monitoring or closed-loop control.
Panel Layout and Mounting
Screw fixing with a depth of 203 mm, width of 185 mm, and height of 306 mm. Clearance requirements: 100 mm above, 10 mm in front, 75 mm below, 5 mm at the side, and 0 mm behind.
Pollution degree 3 per IEC 60947-4-2 means it withstands conductive pollution in industrial environments. Shock resistance rated at 15 g / 11 ms. CE, UL, and CSA approvals cover North American and European installations without additional agency review.