Skip to main content
Siemens 3RW5234-6TC14 — Soft Starters

Siemens 3RW5234-6TC14 SIRIUS Soft Starter, 53 A, 200-480 V

MPN3RW5234-6TC14
Active

Siemens SIRIUS 3RW5234-6TC14 soft starter, 53 A minimum setting, 200-480 V rated voltage, Trip Class 10A/10E/20E, multi-protocol fieldbus.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RW5234-6TC14 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS
3RW5234-6TC14 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)55 kW
Rated motor power at 230 V (40 °C)30 kW
Rated operational current at 40 °C196 A
Rated operational current at 50 °C175 A
Rated operational current at 60 °C154 A
Rated insulation voltage600 V
Minimum settable current (% of Ie)15 %; Relative to smallest settable Ie
Power loss during startup (50 °C)1 291 W
3RW5234-6TC14 — Control & Connection
ParameterValue
Control supply voltage typeAC
Main circuit terminal typebusbar connection
Control circuit wire range, solid1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
Control circuit wire range, finely stranded (with ferrule)1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
Analog outputNo
Auxiliary contact rated current, AC-15 at 250 V3 A
Auxiliary contact rating (UL)R300-B300
Control supply voltage tolerance, AC 50 Hz (max.)10 %
Control supply voltage tolerance, AC 50 Hz (min.)-15 %
Control supply voltage tolerance, AC 60 Hz (max.)10 %
Control supply voltage tolerance, AC 60 Hz (min.)-15 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
Operating voltage tolerance, inside-delta (max.)10 %
Operating voltage tolerance, inside-delta (min.)-15 %
3RW5234-6TC14 — Protection & Features
ParameterValue
Motor overload protectionYes; Full motor protection (thermistor motor protection and electronic motor overload protection)
Thermistor motor protectionYes; Type A PTC or Klixon / Thermoclick
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2
3RW5234-6TC14 — Mechanical
ParameterValue
Height306 mm
Width185 mm
Depth203 mm
Weight6.6 kg
Mounting positionwith vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm
3RW5234-6TC14 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude5 000 m; Derating as of 1000 m, see catalog
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)
3RW5234-6TC14 — Specifications
ParameterValue
Trip ClassCLASS 10A (default) / 10E / 20E; acc. to IEC 60947-4-2
Number Of Controlled Phases3
Utilization category according to IEC 60947-4-2AC 53a
Product Feature Integrated Bypass Contact SystemYes
Start-Up Ramp Time Of Soft Starter0 ... 20 s
3RW5234-6TC14 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable130 ... 700 %
Starting Voltage [%]30 ... 100 %
Stopping Voltage [%]50 %; non-adjustable

Product details

The Siemens 3RW5234-6TC14 is a SIRIUS soft starter sized for a minimum motor current setting of 53 A across a rated voltage range of 200 to 480 V. The Trip Class defaults to CLASS 10A per IEC 60947-4-2, with selectable 10E and 20E curves — the 10A default handles standard pump and fan starts where the motor reaches full speed within 10 seconds; switching to 20E buys you extra thermal capacity for high-inertia loads like centrifuges or crushers that need a longer ramp. The Soft Torque and Pump Ramp Down features are specifically tuned for fluid-handling applications, reducing pressure surges on start and preventing water hammer on stop.

Fieldbus selection and panel integration

This unit carries onboard PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET standard — so it drops into nearly any automation architecture without an external gateway. PROFIenergy is supported in connection with the PROFINET communication module, which matters for energy-aware production lines that need to power down loads during breaks. The free-air clearances: 100 mm upwards, 10 mm forwards, 0 mm backwards, 75 mm downwards, and 5 mm at the side — tight enough for most 306 mm tall × 185 mm wide × 203 mm deep enclosures, but the upward gap is the one to watch if you're stacking multiple units.

Frequently asked questions

What is the difference between Trip Class 10A and 20E on the 3RW5234-6TC14?

Trip Class 10A (the default) allows the motor to reach full speed within 10 seconds of thermal overload protection, suitable for standard pumps and fans. Class 20E extends that thermal budget to 20 seconds for high-inertia loads like crushers or centrifuges that need a longer acceleration ramp. Both are selectable per IEC 60947-4-2.

MPN
3RW5234-6TC14