The 3RW5236-6AC14 mounts via screw fixing to a vertical surface, rotatable ±90° and tiltable ±22.5° front-to-back. Clearance requirements: 100 mm above, 75 mm below, 10 mm forward, 5 mm at the sides, 0 mm backward.
Ratings and trip class
Minimum settable current is 81 A, with a minimum load of 15% relative to the smallest settable Ie. Trip Class 10A default, also configurable to 10E or 20E per IEC 60947-4-2 — meaning it protects standard squirrel-cage motors during start without nuisance tripping on normal acceleration. Operating temperature -25 to +60 °C, with derating required above 40 °C.
Fieldbus and control
Built-in fieldbus support covers PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET standard. PROFIenergy is available when paired with the PROFINET communication module. Analog output configurable as 4-20 mA or 0-10 V via the High Feature HMI. Remote reset by cycling the control supply voltage. Auto-reset is supported. Soft Torque and Pump Ramp Down are standard — useful for reducing mechanical shock on pump starts.