Identification

3RW5243-6TC14 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS

Power & Motor Rating

3RW5243-6TC14 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)110 kW
Rated motor power at 230 V (40 °C)55 kW
Rated operational current at 40 °C364 A
Rated operational current at 50 °C322 A
Rated operational current at 60 °C294 A
Rated insulation voltage600 V
Minimum settable current (% of Ie)15 %; Relative to smallest settable Ie
Power loss during startup (50 °C)2 979 W

Control & Connection

3RW5243-6TC14 — Control & Connection
ParameterValue
Control supply voltage typeAC
Main circuit terminal typebusbar connection
Control circuit wire range, solid1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
Control circuit wire range, finely stranded (with ferrule)1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
Analog outputNo
Auxiliary contact rated current, AC-15 at 250 V3 A
Auxiliary contact rating (UL)R300-B300
Control supply voltage tolerance, AC 50 Hz (max.)10 %
Control supply voltage tolerance, AC 50 Hz (min.)-15 %
Control supply voltage tolerance, AC 60 Hz (max.)10 %
Control supply voltage tolerance, AC 60 Hz (min.)-15 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
Operating voltage tolerance, inside-delta (max.)10 %
Operating voltage tolerance, inside-delta (min.)-15 %

Protection & Features

3RW5243-6TC14 — Protection & Features
ParameterValue
Motor overload protectionYes; Full motor protection (thermistor motor protection and electronic motor overload protection)
Thermistor motor protectionYes; Type A PTC or Klixon / Thermoclick
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2

Mechanical

3RW5243-6TC14 — Mechanical
ParameterValue
Height393 mm
Width210 mm
Depth203 mm
Weight9.9 kg
Mounting positionwith vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm

Environmental

3RW5243-6TC14 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude5 000 m; Derating as of 1000 m, see catalog
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)

Specifications

3RW5243-6TC14 — Specifications
ParameterValue
Trip ClassCLASS 10A (default) / 10E / 20E; acc. to IEC 60947-4-2
Number Of Controlled Phases3
Utilization category according to IEC 60947-4-2AC 53a
Product Feature Integrated Bypass Contact SystemYes
Start-Up Ramp Time Of Soft Starter0 ... 20 s

Electrical

3RW5243-6TC14 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable130 ... 700 %
Starting Voltage [%]30 ... 100 %
Stopping Voltage [%]50 %; non-adjustable

Product details

The Siemens 3RW5243-6TC14 is a SIRIUS soft starter with a minimum settable motor current of 90 A (relative to the smallest settable Ie) and a rated supply voltage of 200 to 480 VAC. Its trip class is configurable: default CLASS 10A, with selectable CLASS 10E or CLASS 20E per IEC 60947-4-2. For heavier loads like crushers or centrifuges, switching to CLASS 20E gives double the trip time, allowing longer acceleration without nuisance tripping. The 90 A minimum current floor means this unit is sized for motor FLCs at or above that level; it will not calibrate down to a smaller motor.

Communication and control

This soft starter supports PROFIBUS, Modbus RTU, Modbus TCP, and EtherNet/IP natively, plus PROFINET standard and PROFIenergy when paired with the optional PROFINET communication module. That makes it a drop-in for most industrial networks without a separate gateway. Remote reset is available by cycling the control supply voltage. Auto-reset is also supported. The unit includes an error logbook, but only with special accessories. There is no analog output and no torque control.

Mounting is by screw fixing on a vertical surface; the unit can be rotated ±90° or tilted ±22.5° front-to-back. Clearance requirements: 100 mm above, 75 mm below, 10 mm forward, 5 mm at the sides, and 0 mm backward. Shock resistance is 15 g / 11 ms (12 g / 11 ms with potential contact lifting). Dimensions: 393 mm high, 210 mm wide, 203 mm deep.

Frequently asked questions

What is the current rating of 3RW5243-6TC14?

The minimum settable motor current is 90 A, relative to the smallest settable Ie. This means the starter is designed for motor full-load currents at or above 90 A.

What trip class does 3RW5243-6TC14 have?

Default trip class is CLASS 10A, with selectable CLASS 10E or CLASS 20E per IEC 60947-4-2.

Does 3RW5243-6TC14 support Modbus or PROFIBUS communication?

Yes, it supports PROFIBUS, Modbus RTU, Modbus TCP, and EtherNet/IP natively. PROFINET standard and PROFIenergy are available with an optional communication module.