SIRIUS 3RW5244-2AC05 — form factor and fieldbus fit
Dimensions are 203 mm deep by 210 mm wide by 393 mm high, fastened by screw fixing, and it mounts on a vertical surface with ±90° rotation and ±22.5° tilt front/back — panel layout needs to account for the 393 mm height and the 100 mm upward / 75 mm downward clearance for airflow. Fieldbus options include PROFIBUS, PROFINET, EtherNet/IP, Modbus RTU, and Modbus TCP — the PROFINET variant supports PROFIenergy when paired with the standard communication module.
Ambient limits and derating
Operating ambient is -25°C to +60°C during operation, with a derating note above 40°C — the 100 A rating is at the base temperature; expect to reduce current if the panel ambient climbs above 40°C. Pollution degree 3 per IEC 60947-4-2 means the unit tolerates conductive pollution in industrial environments, but the 15 g / 11 ms shock rating (with potential contact lifting above 12 g) sets a vibration limit for mounting near heavy machinery.