Skip to main content
Siemens 3RW5245-2TC14 — Soft Starters

Siemens 3RW5245-2TC14 SIRIUS Soft Starter, 135 A, 200-480 V

MPN3RW5245-2TC14
Active

Siemens SIRIUS 3RW5245-2TC14 hybrid soft starter, 135 A minimum, 200-480 VAC, Trip Class 10A, screw fixing, 393 x 210 x 203 mm.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RW5245-2TC14 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS

Power & Motor Rating

3RW5245-2TC14 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)160 kW
Rated motor power at 230 V (40 °C)90 kW
Rated operational current at 40 °C546 A
Rated operational current at 50 °C483 A
Rated operational current at 60 °C442 A
Rated insulation voltage600 V
Minimum settable current (% of Ie)15 %; Relative to smallest settable Ie
Power loss during startup (50 °C)4 471 W

Control & Connection

3RW5245-2TC14 — Control & Connection
ParameterValue
Control supply voltage typeAC
Main circuit terminal typebusbar connection
Control circuit wire range, solid2x (0.25 ... 1.5 mm²)
Control circuit wire range, finely stranded (with ferrule)2x (0.25 ... 1.5 mm²)
Analog outputNo
Auxiliary contact rated current, AC-15 at 250 V3 A
Auxiliary contact rating (UL)R300-B300
Control supply voltage tolerance, AC 50 Hz (max.)10 %
Control supply voltage tolerance, AC 50 Hz (min.)-15 %
Control supply voltage tolerance, AC 60 Hz (max.)10 %
Control supply voltage tolerance, AC 60 Hz (min.)-15 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
Operating voltage tolerance, inside-delta (max.)10 %
Operating voltage tolerance, inside-delta (min.)-15 %

Protection & Features

3RW5245-2TC14 — Protection & Features
ParameterValue
Motor overload protectionYes; Full motor protection (thermistor motor protection and electronic motor overload protection)
Thermistor motor protectionYes; Type A PTC or Klixon / Thermoclick
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2

Mechanical

3RW5245-2TC14 — Mechanical
ParameterValue
Height393 mm
Width210 mm
Depth203 mm
Weight9.9 kg
Mounting positionwith vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm

Environmental

3RW5245-2TC14 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude5 000 m; Derating as of 1000 m, see catalog
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)

Specifications

3RW5245-2TC14 — Specifications
ParameterValue
Trip ClassCLASS 10A (default) / 10E / 20E; acc. to IEC 60947-4-2
Number Of Controlled Phases3
Utilization category according to IEC 60947-4-2AC 53a
Product Feature Integrated Bypass Contact SystemYes
Start-Up Ramp Time Of Soft Starter0 ... 20 s

Electrical

3RW5245-2TC14 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable130 ... 700 %
Starting Voltage [%]30 ... 100 %
Stopping Voltage [%]50 %; non-adjustable

Product details

The Siemens 3RW5245-2TC14 is a SIRIUS-brand hybrid soft starter rated for a minimum operating current of 135 A across a supply range of 200 to 480 VAC. Its default Trip Class 10A per IEC 60947-4-2 means it will disconnect a locked-rotor motor within 10 seconds at 7.2x rated current — fast enough to protect standard squirrel-cage induction motors on pump, fan, or conveyor drives without nuisance tripping on normal start-up. The unit supports Soft Torque and Pump Ramp Down profiles, which reduce mechanical shock on the load train during start and stop — useful on centrifugal pumps where water hammer is a concern.

Fieldbus and communication options

This soft starter ships with onboard PROFIBUS DP and Modbus RTU, plus optional support for Modbus TCP, EtherNet/IP, and PROFINET (the latter with PROFIenergy profile when paired with the standard communication module). That means it can drop into most existing control architectures without a separate gateway — a real time-saver when the line uses mixed protocols and the integrator wants one part number for the panel.

Screw-fixing mount, 393 mm high by 210 mm wide by 203 mm deep. The mounting surface must be vertical; the unit can be rotated ±90° or tilted ±22.5° front-to-back. Clearance requirements: 100 mm above, 75 mm below, 10 mm front, 5 mm side, 0 mm rear — plan the enclosure depth accordingly. Shock-rated to 15 g / 11 ms, which covers most industrial floor vibration.

Frequently asked questions

Is the 3RW5245-2TC14 compatible with 480V supply?

Yes. The rated supply voltage range is 200 to 480 VAC at both 50 Hz and 60 Hz, so it handles 480 V directly without a transformer.

What is the trip class of 3RW5245-2TC14?

Default Trip Class is 10A per IEC 60947-4-2, with selectable alternatives of 10E and 20E. Class 10A means the overload relay will trip within 10 seconds at 7.2x the current setting — standard for most motor protection applications.

Does Siemens 3RW5245-2TC14 support Modbus TCP?

Yes, Modbus TCP is supported alongside Modbus RTU, PROFIBUS DP, EtherNet/IP, and PROFINET (with PROFIenergy).

Where can I buy 3RW5245-2TC14?

This part is sourced to order against an RFQ through independent industrial distribution. Submit a request for current pricing and availability — lead time and stock position are confirmed at quote time.

What is the difference between 3RW5245-2TC14 and 3RW5246-2TC14?

The 3RW5245-2TC14 is rated for a minimum operating current of 135 A, while the 3RW5246-2TC14 is a higher-current variant in the same SIRIUS family. The exact current rating of the 5246 is not listed here; consult the respective datasheet for the specific current threshold difference.

MPN
3RW5245-2TC14