Soft starter for 135 A motor loads, 200-600 V line
The Siemens 3RW5245-6AC05 is a SIRIUS hybrid switching device — a soft starter sized for a minimum motor current of 135 A on a 200 to 600 V supply. The trip class is selectable between CLASS 10A (default), 10E, or 20E per IEC 60947-4-2, meaning you can match the overload protection to the motor start profile: 10A for standard starts, 10E for extended ramp, 20E for high-inertia loads that need a longer acceleration window. It supports PROFIBUS, Modbus RTU, Modbus TCP, and EtherNet/IP natively, plus PROFIenergy in conjunction with a PROFINET communication module. The analog output is configurable as 4-20 mA (default) or 0-10 V via the High Feature HMI.
Mounting is by screw fixing on a vertical surface, rotatable ±90° and tiltable ±22.5° front-to-back. Clearance requirements: 100 mm upwards, 10 mm forwards, 75 mm downwards, 5 mm at the sides, and 0 mm backwards. The enclosure dimensions are 393 mm high, 210 mm wide, 203 mm deep — plan your panel layout accordingly. Shock resistance is 15 g / 11 ms, with potential contact lifting at 12 g / 11 ms.