Skip to main content
Siemens 3RW5246-2TC04 — Soft Starters

Siemens 3RW5246-2TC04 SIRIUS Soft Starter, 160 A, 200-480 V

MPN3RW5246-2TC04
Active

Siemens SIRIUS 3RW5246-2TC04 soft starter, 160 A, 200-480 V, screw fixing, Class 10A/10E/20E, PROFINET, Modbus TCP, EtherNet/IP.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RW5246-2TC04 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS

Power & Motor Rating

3RW5246-2TC04 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)200 kW
Rated motor power at 230 V (40 °C)110 kW
Rated operational current at 40 °C641 A
Rated operational current at 50 °C568 A
Rated operational current at 60 °C519 A
Rated insulation voltage600 V
Minimum settable current (% of Ie)15 %; Relative to smallest settable Ie
Power loss during startup (50 °C)4 706 W

Control & Connection

3RW5246-2TC04 — Control & Connection
ParameterValue
Control supply voltage typeAC/DC
Rated voltage at 50 Hz24 V
Rated voltage at 60 Hz24 V
Main circuit terminal typebusbar connection
Control circuit wire range, solid2x (0.25 ... 1.5 mm²)
Control circuit wire range, finely stranded (with ferrule)2x (0.25 ... 1.5 mm²)
Analog outputNo
Auxiliary contact rated current, AC-15 at 250 V3 A
Auxiliary contact rating (UL)R300-B300
Control supply voltage tolerance, AC 50 Hz (max.)20 %
Control supply voltage tolerance, AC 50 Hz (min.)-20 %
Control supply voltage tolerance, AC 60 Hz (max.)20 %
Control supply voltage tolerance, AC 60 Hz (min.)-20 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
Operating voltage tolerance, inside-delta (max.)10 %
Operating voltage tolerance, inside-delta (min.)-15 %

Protection & Features

3RW5246-2TC04 — Protection & Features
ParameterValue
Motor overload protectionYes; Full motor protection (thermistor motor protection and electronic motor overload protection)
Thermistor motor protectionYes; Type A PTC or Klixon / Thermoclick
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2

Mechanical

3RW5246-2TC04 — Mechanical
ParameterValue
Height393 mm
Width210 mm
Depth203 mm
Weight9.9 kg
Mounting positionwith vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm

Environmental

3RW5246-2TC04 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude5 000 m; Derating as of 1000 m, see catalog
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)

Specifications

3RW5246-2TC04 — Specifications
ParameterValue
Trip ClassCLASS 10A (default) / 10E / 20E; acc. to IEC 60947-4-2
Number Of Controlled Phases3
Utilization category according to IEC 60947-4-2AC 53a
Product Feature Integrated Bypass Contact SystemYes
Start-Up Ramp Time Of Soft Starter0 ... 20 s

Electrical

3RW5246-2TC04 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable130 ... 700 %
Starting Voltage [%]30 ... 100 %
Stopping Voltage [%]50 %; non-adjustable

Product details

What this 160 A SIRIUS soft starter is for

This Siemens SIRIUS 3RW5246-2TC04 is a hybrid soft starter rated for 160 A at 200-480 V, designed to ramp three-phase induction motors up and down without the mechanical shock of a direct-on-line start. It's built for the panel — screw fixing, 393 mm high, 210 mm wide, 203 mm deep — and needs 100 mm clearance above, 75 mm below, and 10 mm forward for airflow and wiring access. The trip class defaults to CLASS 10A per IEC 60947-4-2, but is field-selectable to 10E or 20E, giving you the flexibility to match the motor's thermal withstand curve without swapping hardware.

Fieldbus and control integration

This soft starter ships with onboard PROFINET standard, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFIBUS — no separate communication module to order for those protocols. PROFIenergy is supported when used with the PROFINET standard communication module, letting the plant energy management system shut down the motor during idle periods. Control supply is 24 V DC; remote reset is possible by cycling that control voltage.

Application features: pump ramp down and soft torque

Pump Ramp Down is built in — it extends the deceleration time to prevent water hammer in pumping systems. Soft Torque is also available, useful for reducing mechanical stress on the driven load during start-up. The unit supports firmware updates in the field, so you can add features or fix bugs without swapping the device.

Carries UL, CSA, and CE marking — accepted in North American and European panels without additional certification paperwork. Pollution degree 3 per IEC 60947-4-2, meaning it's rated for the conductive-dust and moisture conditions typical in industrial control rooms.

MPN
3RW5246-2TC04