Skip to main content
Siemens 3RW5246-2TC14 — Soft Starters

Siemens 3RW5246-2TC14 SIRIUS Soft Starter, 160 A, 200-480 V

MPN3RW5246-2TC14
Active

Siemens SIRIUS 3RW5246-2TC14 soft starter, 160 A minimum, 200-480 V, Class 10A/10E/20E, screw fixing, 393 x 210 x 203 mm.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RW5246-2TC14 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS

Power & Motor Rating

3RW5246-2TC14 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)200 kW
Rated motor power at 230 V (40 °C)110 kW
Rated operational current at 40 °C641 A
Rated operational current at 50 °C568 A
Rated operational current at 60 °C519 A
Rated insulation voltage600 V
Minimum settable current (% of Ie)15 %; Relative to smallest settable Ie
Power loss during startup (50 °C)4 706 W

Control & Connection

3RW5246-2TC14 — Control & Connection
ParameterValue
Control supply voltage typeAC
Main circuit terminal typebusbar connection
Control circuit wire range, solid2x (0.25 ... 1.5 mm²)
Control circuit wire range, finely stranded (with ferrule)2x (0.25 ... 1.5 mm²)
Analog outputNo
Auxiliary contact rated current, AC-15 at 250 V3 A
Auxiliary contact rating (UL)R300-B300
Control supply voltage tolerance, AC 50 Hz (max.)10 %
Control supply voltage tolerance, AC 50 Hz (min.)-15 %
Control supply voltage tolerance, AC 60 Hz (max.)10 %
Control supply voltage tolerance, AC 60 Hz (min.)-15 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
Operating voltage tolerance, inside-delta (max.)10 %
Operating voltage tolerance, inside-delta (min.)-15 %

Protection & Features

3RW5246-2TC14 — Protection & Features
ParameterValue
Motor overload protectionYes; Full motor protection (thermistor motor protection and electronic motor overload protection)
Thermistor motor protectionYes; Type A PTC or Klixon / Thermoclick
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2

Mechanical

3RW5246-2TC14 — Mechanical
ParameterValue
Height393 mm
Width210 mm
Depth203 mm
Weight9.9 kg
Mounting positionwith vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm

Environmental

3RW5246-2TC14 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude5 000 m; Derating as of 1000 m, see catalog
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)

Specifications

3RW5246-2TC14 — Specifications
ParameterValue
Trip ClassCLASS 10A (default) / 10E / 20E; acc. to IEC 60947-4-2
Number Of Controlled Phases3
Utilization category according to IEC 60947-4-2AC 53a
Product Feature Integrated Bypass Contact SystemYes
Start-Up Ramp Time Of Soft Starter0 ... 20 s

Electrical

3RW5246-2TC14 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable130 ... 700 %
Starting Voltage [%]30 ... 100 %
Stopping Voltage [%]50 %; non-adjustable

Product details

160 A minimum, 200-480 V — SIRIUS soft starter for motor starting

The Siemens 3RW5246-2TC14 is a SIRIUS-branded hybrid switching device — a soft starter rated for a minimum operating current of 160 A and a voltage range of 200 to 480 V. This is the minimum current the unit can regulate; actual motor full-load current must be set within the device's adjustable range above this floor. Trip class is configurable: default Class 10A, with selectable 10E and 20E per IEC 60947-4-2.

Fieldbus-ready with PROFIBUS, PROFINET, Modbus, EtherNet/IP

The 3RW5246-2TC14 supports PROFIBUS, PROFINET standard, Modbus RTU, Modbus TCP, and EtherNet/IP natively. This means it drops into most common industrial networks without an external gateway — the integrator picks the protocol at configuration, not at procurement. PROFIenergy is available when paired with the PROFINET standard communication module, enabling energy-saving pauses during idle periods. The unit also logs errors to an internal logbook (requires the special accessory), which helps during commissioning fault tracing.

Lifecycle status is active (current production). No stock-holding claim — sourced per RFQ. Approvals include CE marking, UL, and CSA — the unit is accepted in North American and European regulatory jurisdictions without additional certification work.

Mounting and clearance — screw fixing, 393 x 210 x 203 mm

Fastening method is screw fixing; the unit measures 393 mm high, 210 mm wide, and 203 mm deep. Mounting position allows vertical surface with ±90° rotation and ±22.5° tilt front/back — flexible for tight panel layouts. Required clearance distances: 100 mm upwards, 10 mm forwards, 0 mm backwards, 75 mm downwards, and 5 mm at the sides. These ensure adequate airflow for the 160 A minimum rating and prevent thermal stacking in multi-unit enclosures.

Operating temperature and derating — -25 to +60 °C

At elevated temperatures the continuous current capability drops — the derating curve in the manual governs the actual limit for the 160 A minimum setting. Shock resistance is 15 g / 11 ms, with potential contact lifting at 12 g / 11 ms — relevant for installations near heavy rotating equipment or in mobile applications.

MPN