Skip to main content
Siemens 3RW5246-6TC05 — Soft Starters

Siemens 3RW5246-6TC05 SIRIUS Soft Starter, 160 A, 200-600 V

MPN3RW5246-6TC05
Active

Siemens SIRIUS 3RW5246-6TC05 soft starter, 160 A minimum motor rating, 200-600 V, Class 10A/10E/20E, multi-protocol fieldbus, screw fixing.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RW5246-6TC05 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS

Power & Motor Rating

3RW5246-6TC05 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)200 kW
Rated motor power at 230 V (40 °C)110 kW
Rated operational current at 40 °C641 A
Rated operational current at 50 °C568 A
Rated operational current at 60 °C519 A
Rated insulation voltage600 V
Minimum settable current (% of Ie)15 %; Relative to smallest settable Ie
Power loss during startup (50 °C)4 706 W

Control & Connection

3RW5246-6TC05 — Control & Connection
ParameterValue
Control supply voltage typeAC/DC
Rated voltage at 50 Hz24 V
Rated voltage at 60 Hz24 V
Main circuit terminal typebusbar connection
Control circuit wire range, solid1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
Control circuit wire range, finely stranded (with ferrule)1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
Analog outputNo
Auxiliary contact rated current, AC-15 at 250 V3 A
Auxiliary contact rating (UL)R300-B300
Control supply voltage tolerance, AC 50 Hz (max.)20 %
Control supply voltage tolerance, AC 50 Hz (min.)-20 %
Control supply voltage tolerance, AC 60 Hz (max.)20 %
Control supply voltage tolerance, AC 60 Hz (min.)-20 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
Operating voltage tolerance, inside-delta (max.)10 %
Operating voltage tolerance, inside-delta (min.)-15 %

Protection & Features

3RW5246-6TC05 — Protection & Features
ParameterValue
Motor overload protectionYes; Full motor protection (thermistor motor protection and electronic motor overload protection)
Thermistor motor protectionYes; Type A PTC or Klixon / Thermoclick
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2

Mechanical

3RW5246-6TC05 — Mechanical
ParameterValue
Height393 mm
Width210 mm
Depth203 mm
Weight9.9 kg
Mounting positionwith vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm

Environmental

3RW5246-6TC05 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude5 000 m; Derating as of 1000 m, see catalog
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)

Specifications

3RW5246-6TC05 — Specifications
ParameterValue
Trip ClassCLASS 10A (default) / 10E / 20E; acc. to IEC 60947-4-2
Number Of Controlled Phases3
Utilization category according to IEC 60947-4-2AC 53a
Product Feature Integrated Bypass Contact SystemYes
Start-Up Ramp Time Of Soft Starter0 ... 20 s

Electrical

3RW5246-6TC05 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable130 ... 700 %
Starting Voltage [%]30 ... 100 %
Stopping Voltage [%]50 %; non-adjustable

Product details

160 A minimum, 200-600 V — sized for the motor, not the line

The Siemens 3RW5246-6TC05 SIRIUS soft starter is rated for a minimum motor current of 160 A and a supply voltage range of 200 to 600 V. That 160 A floor is the load-side rating — you size the soft starter to the motor FLA, not the incoming feeder. The 200-600 V window covers three-phase systems without a voltage-tap change. Trip Class is selectable: CLASS 10A (default), 10E, or 20E, per IEC 60947-4-2. Class 10A is the standard for standard-start applications — it allows the motor to accelerate within 10 seconds at 6x FLA. Switch to 10E or 20E for high-inertia loads (centrifuges, crushers) where acceleration takes longer. The default 10A setting trips a standard squirrel-cage motor correctly; only change it if the load profile demands it.

Mounting and clearances — panel layout constraints

Envelope dimensions are 203 mm depth, 210 mm width, and 393 mm height. Fastening is screw fixing — no DIN-rail clip. Required clearances: 100 mm upwards, 10 mm forwards, 0 mm backwards, 75 mm downwards, and 5 mm at the side. The 0 mm rear clearance means you can mount it flush against a back panel — useful for tight enclosures. The 100 mm top clearance is for cable bending radius and heat dissipation; respect it or the 160 A rating derates.

Frequently asked questions

Can the 3RW5246-6TC05 communicate via PROFIBUS, Modbus, or EtherNet/IP?

Yes, the 3RW5246-6TC05 supports PROFIBUS, Modbus RTU, Modbus TCP, and EtherNet/IP onboard. PROFINET is also supported, with PROFIenergy available via the PROFINET communication module.

MPN
3RW5246-6TC05