Skip to main content
Siemens 3RW5247-2TC05 — Soft Starters

Siemens 3RW5247-2TC05 SIRIUS Soft Starter, 200 A

MPN3RW5247-2TC05
Active

Siemens SIRIUS 3RW5247-2TC05 soft starter, 200 A minimum, Trip Class 10A/10E/20E, 200–600 V, with PROFIBUS, Modbus RTU/TCP, EtherNet/IP, PROFINET, screw fixing, 203 × 210 × 393 mm.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RW5247-2TC05 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS

Power & Motor Rating

3RW5247-2TC05 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)250 kW
Rated motor power at 230 V (40 °C)132 kW
Rated operational current at 40 °C814 A
Rated operational current at 50 °C721 A
Rated operational current at 60 °C658 A
Rated insulation voltage600 V
Minimum settable current (% of Ie)15 %; Relative to smallest settable Ie
Power loss during startup (50 °C)6 604 W

Control & Connection

3RW5247-2TC05 — Control & Connection
ParameterValue
Control supply voltage typeAC/DC
Rated voltage at 50 Hz24 V
Rated voltage at 60 Hz24 V
Main circuit terminal typebusbar connection
Control circuit wire range, solid2x (0.25 ... 1.5 mm²)
Control circuit wire range, finely stranded (with ferrule)2x (0.25 ... 1.5 mm²)
Analog outputNo
Auxiliary contact rated current, AC-15 at 250 V3 A
Auxiliary contact rating (UL)R300-B300
Control supply voltage tolerance, AC 50 Hz (max.)20 %
Control supply voltage tolerance, AC 50 Hz (min.)-20 %
Control supply voltage tolerance, AC 60 Hz (max.)20 %
Control supply voltage tolerance, AC 60 Hz (min.)-20 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
Operating voltage tolerance, inside-delta (max.)10 %
Operating voltage tolerance, inside-delta (min.)-15 %

Protection & Features

3RW5247-2TC05 — Protection & Features
ParameterValue
Motor overload protectionYes; Full motor protection (thermistor motor protection and electronic motor overload protection)
Thermistor motor protectionYes; Type A PTC or Klixon / Thermoclick
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2

Mechanical

3RW5247-2TC05 — Mechanical
ParameterValue
Height393 mm
Width210 mm
Depth203 mm
Weight9.9 kg
Mounting positionwith vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm

Environmental

3RW5247-2TC05 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude5 000 m; Derating as of 1000 m, see catalog
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)

Specifications

3RW5247-2TC05 — Specifications
ParameterValue
Trip ClassCLASS 10A (default) / 10E / 20E; acc. to IEC 60947-4-2
Number Of Controlled Phases3
Utilization category according to IEC 60947-4-2AC 53a
Product Feature Integrated Bypass Contact SystemYes
Start-Up Ramp Time Of Soft Starter0 ... 20 s

Electrical

3RW5247-2TC05 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable130 ... 700 %
Starting Voltage [%]30 ... 100 %
Stopping Voltage [%]50 %; non-adjustable

Product details

The Siemens 3RW5247-2TC05 is a SIRIUS soft starter rated for a minimum motor current of 200 A, with a Trip Class of CLASS 10A (default), 10E, or 20E per IEC 60947-4-2. The voltage range spans 200 to 600 V, covering 208 V, 400 V, and 480 V common in North American and European panels. Fieldbus support includes PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET — five protocols on one unit, so it drops into existing control architectures without a gateway. PROFIenergy is supported in conjunction with a PROFINET communication module, useful for energy-management profiles in automated lines. For a tire-curing press environment where ambient near the panel can hit 50 °C, plan the derate curve into the motor full-load current calculation. The 15 g / 11 ms shock resistance (with potential contact lifting at 12 g) means it holds up on vibrating machinery skids.

Screw fixing is the fastening method — no DIN-rail clip on this frame size. The mounting surface must be vertical, with ±90° rotatable and ±22.5° tiltable to front and back. Clearance requirements: 100 mm upwards, 10 mm forwards, 0 mm backwards, 75 mm downwards, 5 mm at the side. The 393 mm height and 210 mm width mean it fills a substantial portion of a 600 mm wide enclosure; verify gland-plate clearance for the 203 mm depth before laying out the backpanel.

Frequently asked questions

Does 3RW5247-2TC05 support PROFIBUS or Modbus?

Yes, it supports PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET — five fieldbus protocols on the same unit. PROFIenergy is available when paired with a PROFINET communication module.

MPN