Siemens 3RW5247-2TC14 — Soft Starters

Siemens 3RW5247-2TC14 SIRIUS Soft Starter, 200 A, 200-480 V

MPN3RW5247-2TC14
Active

Siemens SIRIUS 3RW5247-2TC14 soft starter, 200 A minimum, 200-480 V rated, Class 10A/10E/20E, PROFIBUS/Modbus/EtherNet/IP/PROFINET, screw fixing, 393x210x203 mm.

StockContact for availability
Lead time3-5 Days wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

3RW5247-2TC14 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS

Power & Motor Rating

3RW5247-2TC14 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)250 kW
Rated motor power at 230 V (40 °C)132 kW
Rated operational current at 40 °C814 A
Rated operational current at 50 °C721 A
Rated operational current at 60 °C658 A
Rated insulation voltage600 V
Minimum settable current (% of Ie)15 %; Relative to smallest settable Ie
Power loss during startup (50 °C)6 604 W

Control & Connection

3RW5247-2TC14 — Control & Connection
ParameterValue
Control supply voltage typeAC
Main circuit terminal typebusbar connection
Control circuit wire range, solid2x (0.25 ... 1.5 mm²)
Control circuit wire range, finely stranded (with ferrule)2x (0.25 ... 1.5 mm²)
Analog outputNo
Auxiliary contact rated current, AC-15 at 250 V3 A
Auxiliary contact rating (UL)R300-B300
Control supply voltage tolerance, AC 50 Hz (max.)10 %
Control supply voltage tolerance, AC 50 Hz (min.)-15 %
Control supply voltage tolerance, AC 60 Hz (max.)10 %
Control supply voltage tolerance, AC 60 Hz (min.)-15 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
Operating voltage tolerance, inside-delta (max.)10 %
Operating voltage tolerance, inside-delta (min.)-15 %

Protection & Features

3RW5247-2TC14 — Protection & Features
ParameterValue
Motor overload protectionYes; Full motor protection (thermistor motor protection and electronic motor overload protection)
Thermistor motor protectionYes; Type A PTC or Klixon / Thermoclick
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2

Mechanical

3RW5247-2TC14 — Mechanical
ParameterValue
Height393 mm
Width210 mm
Depth203 mm
Weight9.9 kg
Mounting positionwith vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm

Environmental

3RW5247-2TC14 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude5 000 m; Derating as of 1000 m, see catalog
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)

Specifications

3RW5247-2TC14 — Specifications
ParameterValue
Trip ClassCLASS 10A (default) / 10E / 20E; acc. to IEC 60947-4-2
Number Of Controlled Phases3
Utilization category according to IEC 60947-4-2AC 53a
Product Feature Integrated Bypass Contact SystemYes
Start-Up Ramp Time Of Soft Starter0 ... 20 s

Electrical

3RW5247-2TC14 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable130 ... 700 %
Starting Voltage [%]30 ... 100 %
Stopping Voltage [%]50 %; non-adjustable

Product details

SIRIUS soft starter for motor starting duty

The Siemens 3RW5247-2TC14 is a SIRIUS-brand hybrid switching device — a soft starter rated for a minimum operating current of 200 A and a rated voltage range of 200 to 480 V. It is designed to ramp motors up and down smoothly, reducing mechanical stress and inrush current on conveyors, pumps, and compressors. Trip class is configurable: default CLASS 10A, with options for 10E and 20E per IEC 60947-4-2.

Fieldbus and control integration

Onboard communication includes PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET standard — plus PROFIenergy support when paired with the PROFINET communication module. This covers most plant-floor networks without an external gateway. Remote reset is available by cycling the control supply voltage. Auto-reset is also supported, which can restart the motor after a fault clears — useful for unattended pumping stations.

Mounting and environmental limits

Clearance requirements: 100 mm above, 75 mm below, 10 mm forward, 5 mm at the sides, 0 mm backward — plan the enclosure depth accordingly. Shock resistance is 15 g / 11 ms, dropping to 12 g / 11 ms if contact lifting is a concern.

Sourcing and lifecycle status

Approvals include CE, UL, and CSA — accepted in North American and European panels without additional certification work.

Frequently asked questions

What compliance documentation does Siemens provide for 3RW5247-2TC14?

The unit carries CE, UL, and CSA approvals. These cover the IEC 60947-4-2 standard for soft starters and the relevant North American safety requirements.

MPN