Skip to main content
Siemens 3RW5516-1HA14 — Soft Starters

Siemens 3RW5516-1HA14 Soft Starter, ATEX, 200-480 V, Trip Cl

MPN3RW5516-1HA14
Active

Siemens SIRIUS 3RW55 soft starter, order code 3RW5516-1HA14, ATEX and IECEx certified, rated 200-480 V, trip class 10A/10E, with PROFIBUS, Modbus RTU/TCP, and EtherNet/IP.

$1,159.00Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RW5516-1HA14 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS
3RW5516-1HA14 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)15 kW
Rated motor power at 230 V (40 °C)7.5 kW
Rated operational current at 40 °C55.4 A
Rated operational current at 50 °C49 A
Rated operational current at 60 °C45 A
Rated insulation voltage480 V
Minimum settable current (% of Ie)10 %; Relative to set Ie
Power loss during startup (50 °C)437 W
3RW5516-1HA14 — Control & Connection
ParameterValue
Control supply voltage typeAC
Main circuit terminal typescrew-type terminals
Control circuit wire range, solid1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
Control circuit wire range, finely stranded (with ferrule)1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
Analog outputYes; 4 ... 20 mA (default) / 0 ... 10 V
Auxiliary contact rated current, AC-15 at 250 V3 A
Auxiliary contact rating (UL)R300-B300
Control supply voltage tolerance, AC 50 Hz (max.)10 %
Control supply voltage tolerance, AC 50 Hz (min.)-15 %
Control supply voltage tolerance, AC 60 Hz (max.)10 %
Control supply voltage tolerance, AC 60 Hz (min.)-15 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
Operating voltage tolerance, inside-delta (max.)10 %
Operating voltage tolerance, inside-delta (min.)-15 %
3RW5516-1HA14 — Protection & Features
ParameterValue
Motor overload protectionYes; Full motor protection (thermistor motor protection and electronic motor overload protection) / When using the motor overload protection according to ATEX, an upstream contactor is required in inside-delta circuit.
Thermistor motor protectionYes; Type A PTC or Klixon / Thermoclick
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2
3RW5516-1HA14 — Mechanical
ParameterValue
Height275 mm
Width170 mm
Depth152 mm
Weight2.6 kg
Mounting positionVertical (can be rotated +/- 90° and tilted forward or backward +/- 22.5°)
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm
3RW5516-1HA14 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude5 000 m; Derating as of 1000 m, see catalog
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)
3RW5516-1HA14 — Specifications
ParameterValue
Trip ClassCLASS 10A / 10E (default) / 20E / 30E; acc. to IEC 60947-4-2
Number Of Controlled Phases3
Utilization category according to IEC 60947-4-2AC 53a
Product Feature Integrated Bypass Contact SystemYes
Start-Up Ramp Time Of Soft Starter0 ... 360 s
Ramp-Down Time Of Soft Starter0 ... 360 s
3RW5516-1HA14 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable125 ... 800 %
Starting Voltage [%]20 ... 100 %
Stopping Voltage [%]50 %; non-adjustable

Product details

The Siemens 3RW5516-1HA14 is a SIRIUS 3RW55 soft starter designed for three-phase induction motors in industrial applications. It carries ATEX and IECEx certification, meaning it is approved for use in potentially explosive atmospheres — a key requirement for chemical, oil and gas, or grain-handling lines where a standard soft starter would be a safety risk. Rated for 200-480 V and configurable for trip classes 10A, 10E (default), 20E, or 30E per IEC 60947-4-2. The trip class determines how long the starter can carry locked-rotor current during start; Class 10A is the tightest, protecting motors with short acceleration times, while Class 30E suits high-inertia loads like centrifuges or long conveyors.

Fieldbus and control integration

This unit includes onboard PROFIBUS, Modbus RTU, Modbus TCP, and EtherNet/IP — covering the three dominant industrial Ethernet protocols plus legacy PROFIBUS. That means it drops into a Rockwell, Siemens, or Schneider control architecture without a gateway. PROFIenergy support is available when paired with a PROFINET communication module, allowing the drive to shed standby power during production pauses. The event list and error logbook store the last several fault events locally, which speeds troubleshooting on a line-down call.

The 3RW5516-1HA14 measures 275 mm high, 170 mm wide, and 152 mm deep. Screw terminals accept solid conductors: two per phase for 1.0-2.5 mm² and two for 2.5-10 mm². Clearance requirements: 100 mm above, 75 mm below, 10 mm forward, 5 mm to the side, and zero backward. These are the minimum free-air spaces needed for heat dissipation; crowding the enclosure raises the ambient temperature and derates the unit.

The part carries current approvals (UL, CSA, CE) and supports firmware updates.

Frequently asked questions

Is the 3RW5516-1HA14 ATEX certified?

Yes, the evidence lists ATEX certification and IECEx certification, so it is approved for use in hazardous areas requiring those standards.

What trip classes are available on this soft starter?

It supports CLASS 10A, 10E (default), 20E, and 30E per IEC 60947-4-2. Class 10A is for fast-starting loads; Class 30E handles high-inertia starts.

What fieldbus protocols does it support?

Onboard protocols include PROFIBUS, Modbus RTU, Modbus TCP, and EtherNet/IP. PROFIenergy is supported with a PROFINET communication module.

What are the mounting dimensions and clearance requirements?

The unit is 275 mm high, 170 mm wide, 152 mm deep. Clearances: 100 mm above, 75 mm below, 10 mm forward, 5 mm to the side, 0 mm backward.

Does it have UL and CSA approvals?

Yes, UL approval and CSA approval are listed, along with CE marking.

MPN