Siemens 3RW5524-1HA04 Soft Starter, ATEX, 200-480 V, Active

MPN3RW5524-1HA04
Active

Siemens 3RW5524-1HA04 soft starter, ATEX and IECEx certified, 200-480 V rated, trip class 10A/10E/20E/30E, screw terminals, Modbus RTU/TCP, EtherNet/IP, PROFIBUS, 185×306×203 mm.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RW5524-1HA04 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS
3RW5524-1HA04 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)22 kW
Rated motor power at 230 V (40 °C)11 kW
Rated operational current at 40 °C81.4 A
Rated operational current at 50 °C72 A
Rated operational current at 60 °C62.7 A
Rated insulation voltage480 V
Minimum settable current (% of Ie)10 %; Relative to set Ie
Power loss during startup (50 °C)504 W
3RW5524-1HA04 — Control & Connection
ParameterValue
Control supply voltage typeAC/DC
Rated voltage at 50 Hz24 V
Rated voltage at 60 Hz24 V
Main circuit terminal typebox terminal
Control circuit wire range, solid1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
Control circuit wire range, finely stranded (with ferrule)1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
Analog outputYes; 4 ... 20 mA (default) / 0 ... 10 V
Auxiliary contact rated current, AC-15 at 250 V3 A
Auxiliary contact rating (UL)R300-B300
Control supply voltage tolerance, AC 50 Hz (max.)20 %
Control supply voltage tolerance, AC 50 Hz (min.)-20 %
Control supply voltage tolerance, AC 60 Hz (max.)20 %
Control supply voltage tolerance, AC 60 Hz (min.)-20 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
Operating voltage tolerance, inside-delta (max.)10 %
Operating voltage tolerance, inside-delta (min.)-15 %
3RW5524-1HA04 — Protection & Features
ParameterValue
Motor overload protectionYes; Full motor protection (thermistor motor protection and electronic motor overload protection) / When using the motor overload protection according to ATEX, an upstream contactor is required in inside-delta circuit.
Thermistor motor protectionYes; Type A PTC or Klixon / Thermoclick
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2
3RW5524-1HA04 — Mechanical
ParameterValue
Height306 mm
Width185 mm
Depth203 mm
Weight5.5 kg
Mounting positionVertical (can be rotated +/- 90° and tilted forward or backward +/- 22.5°)
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm
3RW5524-1HA04 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude5 000 m; Derating as of 1000 m, see catalog
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)
3RW5524-1HA04 — Specifications
ParameterValue
Trip ClassCLASS 10A / 10E (default) / 20E / 30E; acc. to IEC 60947-4-2
Number Of Controlled Phases3
Utilization category according to IEC 60947-4-2AC 53a
Product Feature Integrated Bypass Contact SystemYes
Start-Up Ramp Time Of Soft Starter0 ... 360 s
Ramp-Down Time Of Soft Starter0 ... 360 s
3RW5524-1HA04 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable125 ... 800 %
Starting Voltage [%]20 ... 100 %
Stopping Voltage [%]50 %; non-adjustable

Product details

ATEX and IECEx certified soft starter for hazardous-area motor control

The 3RW5524-1HA04 carries both ATEX and IECEx certification, meaning it can be installed in Zone 1 or Zone 2 hazardous areas without an additional explosion-proof enclosure for the starter itself — the certification covers the device as part of the motor circuit. Rated 200-480 V, this unit covers the common global industrial voltage band from 208 V North American to 400 V European and 480 V heavy-industrial feeds, with a single soft starter order code that avoids voltage-range variants. Trip class is selectable between CLASS 10A, 10E (default), 20E, and 30E per IEC 60947-4-2 — the 10A setting protects standard squirrel-cage motors with short acceleration times, while 30E handles high-inertia loads like centrifuges or crushers that need a longer ramp.

Fieldbus connectivity and commissioning flexibility

Built-in support for Modbus RTU, Modbus TCP, EtherNet/IP, and PROFIBUS means this soft starter talks directly to the most common PLC networks without an external gateway — the integrator picks the protocol at commissioning, not at ordering. The analog output can be configured for 4-20 mA or 0-10 V, feeding motor current or torque data to a remote SCADA or drive controller without an additional signal conditioner. PROFIenergy support (via PROFINET communication modules) allows the soft starter to participate in energy management profiles during idle periods — useful for production lines that cycle between active and standby states.

Active production and sourcing posture

Global approvals include UL, CSA, and CE marking, covering North American and European regulatory acceptance without additional certification steps.

Panel integration and environmental limits

Dimensions are 185 mm wide, 306 mm high, and 203 mm deep — the unit fits a standard 600 mm deep enclosure with clearance for wiring and cooling. Minimum clearance requirements: 100 mm above, 75 mm below, 10 mm front, 5 mm sides, 0 mm rear. Screw terminals for power and control wiring — no special crimp tooling needed, and the terminal layout matches the standard Siemens 3RW5 family footprint for panel retrofit.

Frequently asked questions

What trip classes does the 3RW5524-1HA04 support?

The soft starter supports selectable trip classes CLASS 10A, 10E (default), 20E, and 30E per IEC 60947-4-2. CLASS 10A is for standard motors with short acceleration, while 30E handles high-inertia loads like centrifuges or crushers.

What fieldbus protocols does the 3RW5524-1HA04 support natively?

It supports Modbus RTU, Modbus TCP, EtherNet/IP, and PROFIBUS without external gateways. It also supports PROFIenergy via PROFINET communication modules for energy management during idle periods.

What are the mounting clearances required for the 3RW5524-1HA04?

Minimum clearances: 100 mm above, 75 mm below, 10 mm front, 5 mm at the sides, and 0 mm rear. The unit dimensions are 185 mm wide, 306 mm high, and 203 mm deep.

MPN