What this soft starter delivers
The 3RW5526-3HF14: Trip class is configurable as CLASS 10A, 10E (default), 20E, or 30E per IEC 60947-4-2, letting you match the thermal protection to the load — pump, fan, or conveyor. Starting profiles include voltage ramp, torque control, pump ramp down, breakaway pulse, and DC braking — covers soft start, controlled stop, and jogging.
Fieldbus and control integration
Supports PROFIBUS, Modbus RTU, Modbus TCP, and EtherNet/IP — drops into existing control networks without a separate gateway module. Analog output configurable as 4-20 mA or 0-10 V for motor current or torque feedback to the PLC or drive controller. Event list, error logbook, and trace function built in — useful for commissioning and fault analysis without external software.
Approvals and compliance
CE marked, UL and CSA approved — accepted in North American and European installations without additional agency review. ATEX and IECEx certification (Yes) means this unit can start motors in Zone 1 or Zone 2 classified areas when properly installed with the matching motor and cabling.
Panel mounting and clearances
Dimensions are 306 mm height, 185 mm width, 203 mm depth — fits standard 600 mm deep enclosures with room for wiring ducts. Minimum clearance requirements: 100 mm above, 75 mm below, 5 mm sides, 10 mm front, 0 mm rear — plan the panel layout accordingly for airflow and heat dissipation.