Siemens 3RW5534-6HF14 — Soft Starters

Siemens 3RW5534-6HF14 SIRIUS Soft Starter, ATEX, 200-480V

MPN3RW5534-6HF14
Active

Siemens SIRIUS 3RW5534-6HF14 soft starter, ATEX/IECEx certified, rated 200-480 V, trip class CLASS 10A/10E/20E/30E, screw terminals, PROFIBUS/Modbus/EtherNet/IP.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RW5534-6HF14 — Identification
ParameterValue
Product designationFailsafe soft starters
Product brand nameSIRIUS
3RW5534-6HF14 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)55 kW
Rated motor power at 230 V (40 °C)30 kW
Rated operational current at 40 °C196 A
Rated operational current at 50 °C175 A
Rated operational current at 60 °C154 A
Rated insulation voltage480 V
Minimum settable current (% of Ie)10 %; Relative to set Ie
Power loss during startup (50 °C)1 279 W
3RW5534-6HF14 — Control & Connection
ParameterValue
Control supply voltage typeAC
Main circuit terminal typebusbar connection
Control circuit wire range, solid1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
Control circuit wire range, finely stranded (with ferrule)1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
Analog outputYes; 4 ... 20 mA (default) / 0 ... 10 V
Auxiliary contact rated current, AC-15 at 250 V3 A
Auxiliary contact rating (UL)R300-B300
Control supply voltage tolerance, AC 50 Hz (max.)10 %
Control supply voltage tolerance, AC 50 Hz (min.)-15 %
Control supply voltage tolerance, AC 60 Hz (max.)10 %
Control supply voltage tolerance, AC 60 Hz (min.)-15 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
Operating voltage tolerance, inside-delta (max.)10 %
Operating voltage tolerance, inside-delta (min.)-15 %
3RW5534-6HF14 — Protection & Features
ParameterValue
Motor overload protectionYes; Full motor protection (thermistor motor protection and electronic motor overload protection) / When using the motor overload protection according to ATEX, an upstream contactor is required in inside-delta circuit.
Thermistor motor protectionYes; Type A PTC or Klixon / Thermoclick
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2
3RW5534-6HF14 — Mechanical
ParameterValue
Height306 mm
Width185 mm
Depth203 mm
Weight6.85 kg
Mounting positionVertical (can be rotated +/- 90° and tilted forward or backward +/- 22.5°)
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm
3RW5534-6HF14 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude2 000 m; Derating as of 1000 m, see catalog
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)
3RW5534-6HF14 — Specifications
ParameterValue
Trip ClassCLASS 10A / 10E (default) / 20E / 30E; acc. to IEC 60947-4-2
Number Of Controlled Phases3
Utilization category according to IEC 60947-4-2AC 53a
Product Feature Integrated Bypass Contact SystemYes
Start-Up Ramp Time Of Soft Starter0 ... 360 s
Ramp-Down Time Of Soft Starter0 ... 360 s
3RW5534-6HF14 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable125 ... 800 %
Starting Voltage [%]20 ... 100 %
Stopping Voltage [%]50 %; non-adjustable

Product details

What this soft starter carries for a hazardous-location line

The Siemens 3RW5534-6HF14 is a SIRIUS soft starter with ATEX and IECEx certification, meaning it is approved for installation in explosive atmospheres where gas or dust groups apply — a requirement that narrows the field of available soft starters considerably. Rated 200 … 480 V, it covers the common European and North American motor voltages without a transformer tap change. Trip class is configurable between CLASS 10A / 10E (default), 20E, and 30E per IEC 60947-4-2, so you can match the thermal curve to the motor's starting profile — CLASS 10 for standard induction motors, CLASS 20 or 30 for high-inertia loads like centrifuges or crushers that need a longer ramp.

Fieldbus and safety integration

This soft starter ships with PROFIBUS, Modbus RTU, Modbus TCP, and EtherNet/IP onboard — no separate communication module to order, which saves a slot and a line item. PROFIenergy is supported when paired with a PROFINET communication module. The fail-safe input (1 safe channel) puts the output in a defined safe state — open load circuit — so a safety PLC or safety relay can drop the starter independently of the main control loop. That matters for zones where a guard-door interlock must kill motor torque before an operator can reach in. Remote reset and auto-reset are both available, which lets a control system re-start the motor after a fault without a panel walk — useful for remote pump stations or conveyor lines.

At 306 mm high × 185 mm wide × 203 mm deep, this is a full-frame SIRIUS soft starter — not a compact. Clearance requirements: 100 mm above, 75 mm below, 5 mm at the sides, 10 mm in front, 0 mm behind. The zero rear clearance means it can sit flush against a back panel or gland plate, which helps when you are squeezing a starter into a crowded enclosure. Screw terminals are standard — no spring-cage option on this variant. For a panel builder that means consistent torque values across all power and control connections.

Motor protection and diagnostics

Motor heating model, torque control, voltage ramp, pump ramp down, and breakaway pulse are all built in. The analog output can be configured for 4 … 20 mA or 0 … 10 V to feed a PLC or local indicator with motor current or torque feedback. Accuracy Class 5 per IEC 61557-12 means the current measurement is within 5 % — adequate for overload protection and basic energy monitoring, not for billing-grade metering. The event list, error logbook, and trace function give a technician the sequence of faults leading up to a trip without needing a separate data logger. DC braking is included, which can stop a motor faster than coasting on applications like conveyors or saws where a quick stop reduces mechanical wear.

The part carries CE, UL, and CSA approvals, which means it is accepted in European and North American markets without additional certification work. The B10d value of 500 000 cycles provides a reliability benchmark for safety-function planning.

Frequently asked questions

Does the 3RW5534-6HF14 have ATEX certification for hazardous locations?

Yes, the 3RW5534-6HF14 carries ATEX and IECEx certification, making it suitable for installation in explosive atmospheres where gas or dust groups apply.

Is the 3RW5534-6HF14 fail-safe?

Yes, it has one fail-safe channel that puts the output in a defined safe state — open load circuit — when triggered.

What trip classes does the 3RW5534-6HF14 support?

It supports CLASS 10A / 10E (default), 20E, and 30E per IEC 60947-4-2, configurable to match the motor starting profile.

What fieldbus protocols does the 3RW5534-6HF14 support?

It supports PROFIBUS, Modbus RTU, Modbus TCP, and EtherNet/IP onboard, plus PROFIenergy when paired with a PROFINET communication module.