Skip to main content
Siemens 3RW5535-2HA16 — Soft Starters

Siemens 3RW5535-2HA16

MPN3RW5535-2HA16
Active

SIRIUS soft starter 200-690 V 143 A, 110-250 V AC spring-type terminals

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jun 2026
How we verify every order →

Specifications

Identification

3RW5535-2HA16 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS

Power & Motor Rating

3RW5535-2HA16 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)75 kW
Rated motor power at 230 V (40 °C)37 kW
Rated operational current at 40 °C248 A
Rated operational current at 50 °C222 A
Rated operational current at 60 °C204 A
Rated insulation voltage690 V
Minimum settable current (% of Ie)10 %; Relative to set Ie
Power loss during startup (50 °C)1 795 W

Control & Connection

3RW5535-2HA16 — Control & Connection
ParameterValue
Control supply voltage typeAC
Main circuit terminal typebusbar connection
Control circuit wire range, solid2x (0.25 ... 1.5 mm²)
Control circuit wire range, finely stranded (with ferrule)2x (0.25 ... 1.5 mm²)
Analog outputYes; 4 ... 20 mA (default) / 0 ... 10 V
Auxiliary contact rated current, AC-15 at 250 V3 A
Auxiliary contact rating (UL)R300-B300
Control supply voltage tolerance, AC 50 Hz (max.)10 %
Control supply voltage tolerance, AC 50 Hz (min.)-15 %
Control supply voltage tolerance, AC 60 Hz (max.)10 %
Control supply voltage tolerance, AC 60 Hz (min.)-15 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
Operating voltage tolerance, inside-delta (max.)10 %
Operating voltage tolerance, inside-delta (min.)-15 %

Protection & Features

3RW5535-2HA16 — Protection & Features
ParameterValue
Motor overload protectionYes; Full motor protection (thermistor motor protection and electronic motor overload protection)
Thermistor motor protectionYes; Type A PTC or Klixon / Thermoclick
Adjustable current limitationYes
Inside-delta connectionYes; Only up to 600 V operating voltage
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2

Mechanical

3RW5535-2HA16 — Mechanical
ParameterValue
Height306 mm
Width185 mm
Depth203 mm
Weight8.5 kg
Mounting positionVertical (can be rotated +/- 90° and tilted forward or backward +/- 22.5°)
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm

Environmental

3RW5535-2HA16 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude2 000 m; Derating as of 1000 m, see catalog
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)

Specifications

3RW5535-2HA16 — Specifications
ParameterValue
Trip ClassCLASS 10A / 10E (default) / 20E / 30E; acc. to IEC 60947-4-2
Number Of Controlled Phases3
Utilization category according to IEC 60947-4-2AC 53a
Product Feature Integrated Bypass Contact SystemYes
Start-Up Ramp Time Of Soft Starter0 ... 360 s
Ramp-Down Time Of Soft Starter0 ... 360 s

Electrical

3RW5535-2HA16 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable125 ... 800 %
Starting Voltage [%]20 ... 100 %
Stopping Voltage [%]50 %; non-adjustable
MPN