3RW5544-2HF14 — Identification
ParameterValue
Product designationFailsafe soft starters
Product brand nameSIRIUS
3RW5544-2HF14 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)132 kW
Rated motor power at 230 V (40 °C)75 kW
Rated operational current at 40 °C433 A
Rated operational current at 50 °C381 A
Rated operational current at 60 °C346 A
Rated insulation voltage480 V
Minimum settable current (% of Ie)10 %; Relative to set Ie
Power loss during startup (50 °C)3 176 W
3RW5544-2HF14 — Control & Connection
ParameterValue
Control supply voltage typeAC
Main circuit terminal typebusbar connection
Control circuit wire range, solid2x (0.25 ... 1.5 mm²)
Control circuit wire range, finely stranded (with ferrule)2x (0.25 ... 1.5 mm²)
Analog outputYes; 4 ... 20 mA (default) / 0 ... 10 V
Auxiliary contact rated current, AC-15 at 250 V3 A
Auxiliary contact rating (UL)R300-B300
Control supply voltage tolerance, AC 50 Hz (max.)10 %
Control supply voltage tolerance, AC 50 Hz (min.)-15 %
Control supply voltage tolerance, AC 60 Hz (max.)10 %
Control supply voltage tolerance, AC 60 Hz (min.)-15 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
Operating voltage tolerance, inside-delta (max.)10 %
Operating voltage tolerance, inside-delta (min.)-15 %
3RW5544-2HF14 — Protection & Features
ParameterValue
Motor overload protectionYes; Full motor protection (thermistor motor protection and electronic motor overload protection) / When using the motor overload protection according to ATEX, an upstream contactor is required in inside-delta circuit.
Thermistor motor protectionYes; Type A PTC or Klixon / Thermoclick
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2
3RW5544-2HF14 — Mechanical
ParameterValue
Height393 mm
Width210 mm
Depth203 mm
Weight10.2 kg
Mounting positionVertical (can be rotated +/- 90° and tilted forward or backward +/- 22.5°)
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm
3RW5544-2HF14 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude2 000 m; Derating as of 1000 m, see catalog
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)
3RW5544-2HF14 — Specifications
ParameterValue
Trip ClassCLASS 10A / 10E (default) / 20E / 30E; acc. to IEC 60947-4-2
Number Of Controlled Phases3
Utilization category according to IEC 60947-4-2AC 53a
Product Feature Integrated Bypass Contact SystemYes
Start-Up Ramp Time Of Soft Starter0 ... 360 s
Ramp-Down Time Of Soft Starter0 ... 360 s
3RW5544-2HF14 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable125 ... 800 %
Starting Voltage [%]20 ... 100 %
Stopping Voltage [%]50 %; non-adjustable

Product details

The Siemens 3RW5544-2HF14 soft starter carries ATEX and IECEx certification. Rated voltage is 200 to 480 V, trip class selectable per IEC 60947-4-2. The unit includes a service factor of 1.15, allowing a 15% continuous overload above the rated motor current — useful for pumps or fans that occasionally run above nameplate.

Fieldbus and monitoring

This soft starter supports PROFIBUS, Modbus RTU, Modbus TCP, and EtherNet/IP natively, so it drops into most common industrial networks without an external gateway. PROFINET is available via a communication module, and PROFIenergy is supported with the PROFINET High-Feature module for energy management during idle phases. The analog output can be configured as 4-20 mA or 0-10 V for forwarding motor current or other process values to a PLC or SCADA. Built-in monitoring includes an event list, error logbook, trace function, and motor heating model. The B10d value is 147,000 cycles.

Dimensions are 210 mm wide, 393 mm high, and 203 mm deep. Clearance requirements: 100 mm above, 75 mm below, 10 mm in front, 0 mm behind, 5 mm at the sides. The 0 mm rear clearance means it can sit flush against a backplate, saving enclosure depth. The unit uses spring-cage terminals (no screw terminals), which speeds wiring and resists vibration loosening.

Frequently asked questions

What is 3RW5544-2HF14's ATEX certification?

The part carries ATEX certification (Yes), meaning it is approved for use in potentially explosive atmospheres.

Where can I buy 3RW5544-2HF14?

This part is sourced to order against RFQ. Availability and pricing are confirmed at quote time.

MPN
3RW5544-2HF14