Specifications

Identification

3RW5546-2HA04 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS

Power & Motor Rating

3RW5546-2HA04 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)200 kW
Rated motor power at 230 V (40 °C)110 kW
Rated operational current at 40 °C641 A
Rated operational current at 50 °C568 A
Rated operational current at 60 °C519 A
Rated insulation voltage480 V
Minimum settable current (% of Ie)10 %; Relative to set Ie
Power loss during startup (50 °C)4 694 W

Control & Connection

3RW5546-2HA04 — Control & Connection
ParameterValue
Control supply voltage typeAC/DC
Rated voltage at 50 Hz24 V
Rated voltage at 60 Hz24 V
Main circuit terminal typebusbar connection
Control circuit wire range, solid2x (0.25 ... 1.5 mm²)
Control circuit wire range, finely stranded (with ferrule)2x (0.25 ... 1.5 mm²)
Analog outputYes; 4 ... 20 mA (default) / 0 ... 10 V
Auxiliary contact rated current, AC-15 at 250 V3 A
Auxiliary contact rating (UL)R300-B300
Control supply voltage tolerance, AC 50 Hz (max.)20 %
Control supply voltage tolerance, AC 50 Hz (min.)-20 %
Control supply voltage tolerance, AC 60 Hz (max.)20 %
Control supply voltage tolerance, AC 60 Hz (min.)-20 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
Operating voltage tolerance, inside-delta (max.)10 %
Operating voltage tolerance, inside-delta (min.)-15 %

Protection & Features

3RW5546-2HA04 — Protection & Features
ParameterValue
Motor overload protectionYes; Full motor protection (thermistor motor protection and electronic motor overload protection) / When using the motor overload protection according to ATEX, an upstream contactor is required in inside-delta circuit.
Thermistor motor protectionYes; Type A PTC or Klixon / Thermoclick
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2

Mechanical

3RW5546-2HA04 — Mechanical
ParameterValue
Height393 mm
Width210 mm
Depth203 mm
Weight10.9 kg
Mounting positionVertical (can be rotated +/- 90° and tilted forward or backward +/- 22.5°)
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm

Environmental

3RW5546-2HA04 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude5 000 m; Derating as of 1000 m, see catalog
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)

Specifications

3RW5546-2HA04 — Specifications
ParameterValue
Trip ClassCLASS 10A / 10E (default) / 20E / 30E; acc. to IEC 60947-4-2
Number Of Controlled Phases3
Utilization category according to IEC 60947-4-2AC 53a
Product Feature Integrated Bypass Contact SystemYes
Start-Up Ramp Time Of Soft Starter0 ... 360 s
Ramp-Down Time Of Soft Starter0 ... 360 s

Electrical

3RW5546-2HA04 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable125 ... 800 %
Starting Voltage [%]20 ... 100 %
Stopping Voltage [%]50 %; non-adjustable
MPN
3RW5546-2HA04