3RW5547-2HA06 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS
3RW5547-2HA06 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)250 kW
Rated motor power at 230 V (40 °C)132 kW
Rated operational current at 40 °C814 A
Rated operational current at 50 °C721 A
Rated operational current at 60 °C658 A
Rated insulation voltage690 V
Minimum settable current (% of Ie)10 %; Relative to set Ie
Power loss during startup (50 °C)6 400 W
3RW5547-2HA06 — Control & Connection
ParameterValue
Control supply voltage typeAC/DC
Rated voltage at 50 Hz24 V
Rated voltage at 60 Hz24 V
Main circuit terminal typebusbar connection
Control circuit wire range, solid2x (0.25 ... 1.5 mm²)
Control circuit wire range, finely stranded (with ferrule)2x (0.25 ... 1.5 mm²)
Analog outputYes; 4 ... 20 mA (default) / 0 ... 10 V
Auxiliary contact rated current, AC-15 at 250 V3 A
Auxiliary contact rating (UL)R300-B300
Control supply voltage tolerance, AC 50 Hz (max.)20 %
Control supply voltage tolerance, AC 50 Hz (min.)-20 %
Control supply voltage tolerance, AC 60 Hz (max.)20 %
Control supply voltage tolerance, AC 60 Hz (min.)-20 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
Operating voltage tolerance, inside-delta (max.)10 %
Operating voltage tolerance, inside-delta (min.)-15 %
3RW5547-2HA06 — Protection & Features
ParameterValue
Motor overload protectionYes; Full motor protection (thermistor motor protection and electronic motor overload protection)
Thermistor motor protectionYes; Type A PTC or Klixon / Thermoclick
Adjustable current limitationYes
Inside-delta connectionYes; Only up to 600 V operating voltage
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2
3RW5547-2HA06 — Mechanical
ParameterValue
Height393 mm
Width210 mm
Depth203 mm
Weight10.9 kg
Mounting positionVertical (can be rotated +/- 90° and tilted forward or backward +/- 22.5°)
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm
3RW5547-2HA06 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude2 000 m; Derating as of 1000 m, see catalog
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)
3RW5547-2HA06 — Specifications
ParameterValue
Trip ClassCLASS 10A / 10E (default) / 20E / 30E; acc. to IEC 60947-4-2
Number Of Controlled Phases3
Utilization category according to IEC 60947-4-2AC 53a
Product Feature Integrated Bypass Contact SystemYes
Start-Up Ramp Time Of Soft Starter0 ... 360 s
Ramp-Down Time Of Soft Starter0 ... 360 s
3RW5547-2HA06 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable125 ... 800 %
Starting Voltage [%]20 ... 100 %
Stopping Voltage [%]50 %; non-adjustable

Product details

What this soft starter brings to the panel

The Siemens 3RW5547-2HA06 is a SIRIUS-series soft starter carrying ATEX and IECEx certification. Trip class is configurable from CLASS 10A / 10E (default) through 20E and 30E per IEC 60947-4-2. Rated voltage spans 200 to 690 V. Communication is fully wired for modern factory networks: Modbus RTU, Modbus TCP, PROFIBUS, and EtherNet/IP are all on board. That saves an external gateway and simplifies the control cabinet layout. The unit also supports PROFIenergy in connection with PROFINET Standard and PROFINET High-Feature communication modules, which allows energy-saving pauses during idle periods on automated lines. The 393 x 210 x 203 mm footprint (height x width x depth) plus clearance requirements (100 mm upward, 75 mm downward, 10 mm forward, 5 mm at the side, 0 mm backward) must be factored into the panel layout before cutting the gland plate.

Approvals include CE, UL, and CSA. ATEX and IECEx marks are the main differentiator from standard soft starters.

The adjustable trip class (10A/10E default, 20E, 30E) governs how long the soft starter allows the motor to draw starting current before the thermal model trips. Accuracy class is 5 per IEC 61557-12. Additional motor-control features include DC braking for rapid stopping, voltage ramp for gentle acceleration, pump ramp down to avoid water hammer, torque control, a breakaway pulse to crack stuck loads, and motor heating for anti-condensation in standby. The analog output is configurable as 4-20 mA (default) or 0-10 V, feeding motor current or other process values to a PLC or panel meter. Service factor is 1.15, matching the typical NEMA motor margin.

Frequently asked questions

Is 3RW5547-2HA06 suitable for ATEX environments?

Yes, the 3RW5547-2HA06 carries ATEX and IECEx certification, making it approved for starting motors in potentially explosive atmospheres. This is not a general-purpose unit — the hazardous-area declaration is a core spec.

Does 3RW5547-2HA06 support Modbus TCP communication?

Yes, Modbus TCP is supported natively, along with Modbus RTU, PROFIBUS, and EtherNet/IP. No external gateway is needed for these protocols.