Siemens 3RW5548-6HA14 Soft Starter, 200-480 V, ATEX, Active

MPN3RW5548-6HA14
Active

Siemens 3RW5548-6HA14 soft starter, 200-480 V rated voltage, ATEX and IECEx certified, trip class 10A/10E/20E/30E, screw terminal, 393 x 210 x 203 mm.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RW5548-6HA14 — Identification
ParameterValue
Product designationSoft starter
Product brand nameSIRIUS
3RW5548-6HA14 — Power & Motor Rating
ParameterValue
Rated motor power at 400 V (40 °C)315 kW
Rated motor power at 230 V (40 °C)160 kW
Rated operational current at 40 °C987 A
Rated operational current at 50 °C873 A
Rated operational current at 60 °C796 A
Rated insulation voltage480 V
Minimum settable current (% of Ie)10 %; Relative to set Ie
Power loss during startup (50 °C)8 488 W
3RW5548-6HA14 — Control & Connection
ParameterValue
Control supply voltage typeAC
Main circuit terminal typebusbar connection
Control circuit wire range, solid1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
Control circuit wire range, finely stranded (with ferrule)1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
Analog outputYes; 4 ... 20 mA (default) / 0 ... 10 V
Auxiliary contact rated current, AC-15 at 250 V3 A
Auxiliary contact rating (UL)R300-B300
Control supply voltage tolerance, AC 50 Hz (max.)10 %
Control supply voltage tolerance, AC 50 Hz (min.)-15 %
Control supply voltage tolerance, AC 60 Hz (max.)10 %
Control supply voltage tolerance, AC 60 Hz (min.)-15 %
Control supply frequency tolerance (max.)10 %
Control supply frequency tolerance (min.)-10 %
Operating frequency tolerance (max.)10 %
Operating frequency tolerance (min.)-10 %
Operating voltage tolerance, inside-delta (max.)10 %
Operating voltage tolerance, inside-delta (min.)-15 %
3RW5548-6HA14 — Protection & Features
ParameterValue
Motor overload protectionYes; Full motor protection (thermistor motor protection and electronic motor overload protection) / When using the motor overload protection according to ATEX, an upstream contactor is required in inside-delta circuit.
Thermistor motor protectionYes; Type A PTC or Klixon / Thermoclick
Adjustable current limitationYes
Inside-delta connectionYes
Intrinsic device protectionYes
Pollution degree3, acc. to IEC 60947-4-2
3RW5548-6HA14 — Mechanical
ParameterValue
Height393 mm
Width210 mm
Depth203 mm
Weight10.9 kg
Mounting positionVertical (can be rotated +/- 90° and tilted forward or backward +/- 22.5°)
Fastening methodscrew fixing
Mounting clearance, top100 mm
Mounting clearance, bottom75 mm
Mounting clearance, side5 mm
Mounting clearance, front10 mm
3RW5548-6HA14 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above
Storage / transport temperature range-40 ... +80 °C
Max. installation altitude5 000 m; Derating as of 1000 m, see catalog
Ambient class during operation (IEC 60721)3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
Ambient class during transport (IEC 60721)2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)
3RW5548-6HA14 — Specifications
ParameterValue
Trip ClassCLASS 10A / 10E (default) / 20E / 30E; acc. to IEC 60947-4-2
Number Of Controlled Phases3
Utilization category according to IEC 60947-4-2AC 53a
Product Feature Integrated Bypass Contact SystemYes
Start-Up Ramp Time Of Soft Starter0 ... 360 s
Ramp-Down Time Of Soft Starter0 ... 360 s
3RW5548-6HA14 — Electrical
ParameterValue
Current Limiting Value [%] Adjustable125 ... 800 %
Starting Voltage [%]20 ... 100 %
Stopping Voltage [%]50 %; non-adjustable

Product details

Hazardous-area motor starting with ATEX and IECEx

This Siemens 3RW5548-6HA14 soft starter carries both ATEX and IECEx certification, making it suitable for starting motors in classified hazardous locations where explosive atmospheres may be present. The certification covers the soft starter itself when installed per the manufacturer's instructions — a key requirement for Zone 1/21 and Zone 2/22 installations in chemical, oil and gas, or pharmaceutical plants.

Trip class flexibility for diverse load profiles

The soft starter offers selectable trip classes: CLASS 10A, 10E (default), 20E, and 30E per IEC 60947-4-2. Rated voltage spans 200 to 480 V AC, covering the common low-voltage three-phase networks worldwide. Accuracy Class 5 per IEC 61557-12 means the integrated current measurement and motor protection functions meet metering-grade accuracy — sufficient for energy monitoring and predictive maintenance trending without a separate power meter.

Fieldbus integration and control features

The 3RW5548-6HA14 supports Modbus RTU, Modbus TCP, and EtherNet/IP natively, plus PROFIBUS and PROFINET with the appropriate communication module. This covers the three dominant industrial Ethernet protocols, so it drops into most modern control architectures without a protocol gateway. Built-in control features include voltage ramp start, torque control, pump ramp down for controlled deceleration in fluid systems, a breakaway pulse for stuck loads, and DC braking for rapid stopping. The analog output (4-20 mA or 0-10 V) provides a real-time current or torque signal to the PLC or SCADA. An event list, error logbook, and trace function are onboard for fault diagnosis — useful for field service techs trying to identify the root cause of a trip without connecting a laptop.

Panel layout and clearance requirements

Dimensions are 393 mm height, 210 mm width, and 203 mm depth. The unit requires specific free-space clearances for ventilation and wiring access: 100 mm above, 75 mm below, 10 mm in front, 5 mm at the sides, and 0 mm behind. These clearances must be maintained inside the enclosure to prevent thermal derating and allow cable entry. Wiring is via screw terminals — field-serviceable with standard tools. The service factor of 1.15 means the soft starter can handle 115% of rated current continuously without damage, providing a margin for occasional overloads in continuous-duty applications.

Compliance and approvals for global projects

The soft starter carries CE marking for the European market, UL approval for the US, and CSA approval for Canada. These three approvals cover the majority of industrial installations in North America and Europe, simplifying project compliance documentation. ATEX and IECEx certification are listed directly on the unit, so the declaration of conformity and certificate numbers are available from Siemens for inclusion in hazardous-area equipment registers.

Frequently asked questions

What compliance documentation does Siemens provide for 3RW5548-6HA14?

The unit carries CE marking (European conformity), UL approval (US), CSA approval (Canada), ATEX certification, and IECEx certification. Siemens provides the declaration of conformity, UL/CSA certificates, and ATEX/IECEx certificates with the unit or on request.

What are the clearance requirements for mounting this soft starter in a panel?

The required free-space clearances are: 100 mm above, 75 mm below, 10 mm in front, 5 mm at the sides, and 0 mm behind the unit. These ensure adequate ventilation for heat dissipation and space for cable entry via the screw terminals.

What fieldbus protocols does 3RW5548-6HA14 support?

It supports Modbus RTU, Modbus TCP, and EtherNet/IP natively. PROFIBUS and PROFINET are supported via optional communication modules. PROFIenergy is available in conjunction with PROFINET Standard and PROFINET High-Feature modules.