Siemens 3TK2834-2AL20
MPN3TK2834-2AL20
SIRIUS safety relay with relay enabling circuits (EC) 230 V AC, 45 mm overall width Spring-type terminal EC instantaneous: 2 NO + 2 NC EC delayed: 0 SC: 0 Press control device maximum achieved SIL: 3, PL: e
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026
Specifications
| Parameter | Value |
|---|---|
| Type of electrical connection | spring-loaded terminals |
| Safety device type according to IEC 61508-2 | Type A |
| Type of electrical connection Plug-In socket | Yes |
| Type of voltage of the control supply voltage | AC |
| Type of the Safety-Related wiring of the inputs | two-channel |
| Insulation voltage rated value | 300 V |
| Surge voltage resistance rated value | 4 000 V |
| Thermal current of the switching element with contacts maximum | 6 A |
| Design of the fuse link for short-circuit protection of the NO contacts of the relay outputs required | gL/gG: 6 A, or quick: 10 A |
| Operating frequency maximum | 1 000 1/h |
| Protection class IP of the enclosure | IP20 |
| Mounting position | any |
| Parameter | Value |
|---|---|
| At 24 V | 6 A |
| At 115 V | 5 A |
| At 230 V | 5 A |
| Parameter | Value |
|---|---|
| At 50 Hz | 0.85 ... 1.1 |
| At 60 Hz | 0.85 ... 1.1 |
| At 50 Hz rated value | 230 V |
| At 60 Hz rated value | 230 V |
All specifications
| Parameter | Value |
|---|---|
| Installation environment regarding EMC | This product is suitable for Class A environments only. In household environments, this device can cause unwanted radio interference. The user is required to implement appropriate measures in this case. |
| Installation altitude at height above sea level maximum | 2 000 m |
| DC resistance of the cable maximum | 30 Ω |
| Protection class IP of the terminal | IP20 |
| Shock resistance | 8g / 10 ms |
| EMC emitted interference | EN 60947-5-1 |
| Relative humidity during operation | 10 ... 95 % |
| Touch protection against electrical shock | finger-safe |
| Vibration resistance according to IEC 60068-2-6 | 5 ... 500 Hz: 0,075 mm |
| Depth | 120 mm |
| Width | 45 mm |
| Height | 138.5 mm |
| UL approval | Yes |
| BG BIA approval | Yes |
| According to IEC 61508 | 3 |
| Hardware fault tolerance according to IEC 61508 | 1 |
| Solid | 2x (24 ... 16) |
| At DC | 0.85 ... 1.1 |
| Stranded | 2x (24 ... 16) |
| 2-Channel | 1 |
| Start input | No |
| 1 rated value | 50 Hz |
| 2 rated value | 60 Hz |
| Safety switch | Yes |
| At AC maximum | 100 ms |
| During storage | -40 ... +80 °C |
| Feedback input | Yes |
| Automatic start | No |
| During operation | -25 ... +60 °C |
| Mounting | screw and snap-on mounting |
| Valve monitoring | No |
| Delayed switching | 0 |
| Monitored Start-Up | No |
| Design of the product | for press control units |
| Instantaneous contact | 0 |
| Standstill monitoring | No |
| EMERGENCY OFF function | No |
| Light array monitoring | No |
| Safety-Related circuits | Yes |
| Laser scanner monitoring | No |
| Light barrier monitoring | No |
| With core end processing | 2 x (0.25 ... 1.5 mm²) |
| Rotation speed monitoring | No |
| Tactile sensor monitoring | No |
| Position switch monitoring | Yes |
| Protective door monitoring | No |
| Without core end processing | 2x (0.25 ... 1.5 mm²) |
| Monitoring of floating sensors | Yes |
| EMERGENCY-OFF circuit monitoring | No |
| Safety-Related delayed switching | 0 |
| Pressure-Sensitive mat monitoring | No |
| Monitoring of Non-Floating sensors | No |
| Air pressure according to SN 31205 | 90 ... 106 kPa |
| Product feature Cross-Circuit-Proof | Yes |
| Cascading input (Functional switching) | No |
| Safety-Related instantaneous contact | 4 |
| Category according to EN ISO 13849-1 | 4 |
| Stop category according to EN 60204-1 | 0 |
| Reference code according to EN 61346-2 | F |
| Magnetically operated switch monitoring | No |
| Suitability for interaction press control | Yes |
| For signaling function instantaneous contact | 0 |
| Magnetically operated switch monitoring NC-NC | No |
| Magnetically operated switch monitoring NC-NO | No |
| Electrical endurance (Operating cycles) typical | 100 000 |
| PFHD with high demand rate according to EN 62061 | 1.4E-9 1/h |
| SIL claim limit (subsystem) according to EN 62061 | 3 |
| Mechanical service life (Operating cycles) typical | 10 000 000 |
| Recovery time after opening of the safety circuits typical | 250 ms |
MPN