Skip to main content
Siemens 3TK2845-1BB41 — Safety Relays

Siemens 3TK2845-1BB41

MPN3TK2845-1BB41

SIRIUS SAFETY RELAY WITH ELECTR. RELEASE CIRCUIT (FK) 24V DC, 45.0MM, SCREW TERMINAL, FK INSTANT.: 1S AND 1HL, FK DELAYED:1S AND 1HL 0.05..3S, MK:1HL, AUTOSTART / MONIT. START, MULTIFUNCTION UNIT, MAX. CATEGORY: 4

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3TK2845-1BB41 key specifications
ParameterValue
Mountingscrew and snap-on mounting
Type of electrical connectionscrew-type terminals
Safety device type acc. to IEC 61508-2Type B
Type of electrical connection plug-in socketYes
Type of voltage of the control supply voltageDC
Type of the safety-related wiring of the inputssingle-channel and two-channel
Insulation voltage rated value300 V
Surge voltage resistance rated value4 000 V
Design of the fuse link for short-circuit protection of the NO contacts of the relay outputs requiredgL/gG: 4 A or fast-acting: 4A
Recovery time after power failure typical8 000 ms
Operating frequency maximum2 000 1/h
Protection class IP of the enclosureIP20
3TK2845-1BB41 — By operating voltage
ParameterValue
At 24 V1 A
At 115 V3 A
At 230 V3 A

All specifications

3TK2845-1BB41 additional specifications
ParameterValue
Mounting positionany
Installation environment regarding EMCThis product is suitable for Class A environments only. It can cause undesired radio-frequency interference in residential environments. If this is the case, the user must take appropriate measures.
Installation altitude at height above sea level maximum2 000 m
DC resistance of the cable maximum1 000 Ω
Protection class IP of the terminalIP20
Shock resistance8g / 10 ms and 15g / 5 ms
EMC emitted interferenceIEC 60947-5-1, IEC 60000-4-3, IEC 60000-4-5, IEC 60000-4-6
Relative humidity during operation10 ... 95 %
Protection against electrical shockfinger-safe
Vibration resistance acc. to IEC 60068-2-65 ... 500 Hz: 0,075 mm
Depth88 mm
Width45 mm
Height138.5 mm
UL approvalYes
Acc. to IEC 615083
Hardware fault tolerance acc. to IEC 615081
For delayed release circuit acc. to IEC 61508SIL3
Solid2x (20 ... 14)
At DC0.85 ... 1.15
Typical25 ms
Stranded2x (20 ... 14)
Start inputYes
Safety switchYes
At DC maximum100 ms
During storage-40 ... +80 °C
Feedback inputYes
Automatic startYes
During operation-25 ... +60 °C
Valve monitoringNo
Delayed switching0
At DC rated value24 V
Monitored Start-UpYes
Design of the productfor EMERGENCY-STOP and safety doors
Instantaneous contact1
Standstill monitoringNo
1-Channel or 2-Channel2
EMERGENCY OFF functionYes
Light array monitoringYes
Acc. to EN ISO 13849-1e
Design of the cascadingcascading or in-service switching
Safety-Related circuitsYes
Laser scanner monitoringYes
Light barrier monitoringYes
With core end processing1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
Rotation speed monitoringNo
Tactile sensor monitoringYes
Position switch monitoringYes
Protective door monitoringYes
Of the sensor input minimum45 ms
Air pressure acc. to SN 3120590 ... 106 kPa
Monitoring of floating sensorsYes
Of the cascading input minimum0.045 s
Category acc. to EN ISO 13849-14
EMERGENCY-OFF circuit monitoringYes
Safety-Related delayed switching1
Pressure-sensitive mat monitoringYes
Monitoring of non-floating sensorsYes
Of the ON pushbutton input minimum0.2 s
Product feature cross-circuit-proofYes
Cascading input (Functional switching)Yes
Safety-Related instantaneous contact1
Stop category acc. to DIN EN 60204-10 + 1
Reference code acc. to DIN EN 61346-2F
For enabling circuit at dc-13 at 241 A
Magnetically operated switch monitoringYes
For signaling function at dc-13 at 240.5 A
Suitability for interaction press controlNo
PFHD with high demand rate acc. to EN 620610.0000000069 1/h
For signaling function instantaneous contact0
SIL claim limit (subsystem) acc. to EN 620613
Magnetically operated switch monitoring NC-NCYes
Magnetically operated switch monitoring NC-NONo
Mechanical service life (switching cycles) typical100 000
For delayed release circuit acc. to EN ISO 13849-1e
Recovery time after opening of the safety circuits typical400 ms
MPN