Siemens 3TK2845-1HB42
MPN3TK2845-1HB42
!!! Phased-out product!!! The successor product series is 3SK2 (see FAQ 109747906) SIRIUS safety relay with relay and electronic 24 V DC, 45 mm Screw terminal EC instantaneous: 2 NO EC delayed: 2 SC: 1 Auto-start and monitored start Basic device Maximum achievable PL according to EN 13849-1: e Maximum achievable SIL according to IEC 61508: 3
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026
Specifications
| Parameter | Value |
|---|---|
| Type of electrical connection | screw-type terminals |
| Safety device type according to IEC 61508-2 | Type B |
| Type of electrical connection Plug-In socket | Yes |
| Type of voltage of the control supply voltage | DC |
| Type of the Safety-Related wiring of the inputs | single-channel and two-channel |
| Insulation voltage rated value | 300 V |
| Surge voltage resistance rated value | 4 000 V |
| Design of the fuse link for short-circuit protection of the NO contacts of the relay outputs required | gL/gG: 4 A or fast-acting: 4A |
| Recovery time after power failure typical | 8 s |
| Operating frequency maximum | 2 000 1/h |
| Protection class IP of the enclosure | IP20 |
| Mounting position | any |
| Parameter | Value |
|---|---|
| At 24 V | 1 A |
| At 115 V | 3 A |
| At 230 V | 3 A |
All specifications
| Parameter | Value |
|---|---|
| Installation environment regarding EMC | This product is suitable for Class A environments only. In household environments, this device can cause unwanted radio interference. The user is required to implement appropriate measures in this case. |
| Installation altitude at height above sea level maximum | 2 000 m |
| DC resistance of the cable maximum | 1 000 Ω |
| Protection class IP of the terminal | IP20 |
| Shock resistance | 8g / 10 ms, 15g / 5 ms |
| EMC emitted interference | IEC 60947-5-1, IEC 60000-4-3, IEC 60000-4-5, IEC 60000-4-6 |
| Relative humidity during operation | 10 ... 95 % |
| Touch protection against electrical shock | finger-safe |
| Vibration resistance according to IEC 60068-2-6 | 5 ... 500 Hz: 0,075 mm |
| Depth | 88 mm |
| Width | 45 mm |
| Height | 138.5 mm |
| UL approval | Yes |
| BG BIA approval | Yes |
| According to IEC 61508 | 3 |
| Hardware fault tolerance according to IEC 61508 | 1 |
| For delayed release circuit according to IEC 61508 | SIL3 |
| Solid | 2x (20 ... 14) |
| At DC | 0.85 ... 1.15 |
| Typical | 25 ms |
| Stranded | 2x (20 ... 14) |
| Start input | Yes |
| Safety switch | Yes |
| At DC maximum | 100 ms |
| During storage | -40 ... +80 °C |
| Feedback input | Yes |
| Automatic start | Yes |
| During operation | -25 ... +60 °C |
| Mounting | screw and snap-on mounting |
| Valve monitoring | No |
| Delayed switching | 0 |
| At DC rated value | 24 V |
| Monitored Start-Up | Yes |
| Design of the product | monitored start and autostart |
| Instantaneous contact | 1 |
| Standstill monitoring | No |
| 1-Channel or 2-Channel | 2 |
| EMERGENCY OFF function | Yes |
| Light array monitoring | Yes |
| Design of the cascading | cascading or in-service switching |
| Safety-Related circuits | Yes |
| Laser scanner monitoring | Yes |
| Light barrier monitoring | Yes |
| With core end processing | 1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²) |
| Rotation speed monitoring | No |
| Tactile sensor monitoring | Yes |
| Position switch monitoring | Yes |
| Protective door monitoring | Yes |
| Of the sensor input minimum | 45 ms |
| Monitoring of floating sensors | Yes |
| Of the cascading input minimum | 0.045 s |
| EMERGENCY-OFF circuit monitoring | Yes |
| Safety-Related delayed switching | 1 |
| Pressure-Sensitive mat monitoring | Yes |
| Monitoring of Non-Floating sensors | Yes |
| Air pressure according to SN 31205 | 90 ... 106 kPa |
| Of the ON pushbutton input minimum | 0.2 s |
| Product feature Cross-Circuit-Proof | Yes |
| Cascading input (Functional switching) | Yes |
| Safety-Related instantaneous contact | 1 |
| Category according to EN ISO 13849-1 | 4 |
| For enabling circuit at dc-13 at 24 | 1 A |
| Stop category according to EN 60204-1 | 0 + 1 |
| Reference code according to EN 61346-2 | F |
| Magnetically operated switch monitoring | Yes |
| For signaling function at dc-13 at 24 | 0.5 A |
| Suitability for interaction press control | No |
| For signaling function instantaneous contact | 0 |
| Magnetically operated switch monitoring NC-NC | Yes |
| Magnetically operated switch monitoring NC-NO | No |
| PFHD with high demand rate according to EN 62061 | 6.9E-9 1/h |
| SIL claim limit (subsystem) according to EN 62061 | 3 |
| Mechanical service life (Operating cycles) typical | 100 000 |
| Recovery time after opening of the safety circuits typical | 400 ms |
MPN
3TK2845-1HB42