SIRIUS safety relay with contactor relay enabling circuits (EC) 24 V DC, 90 mm Screw terminal EC instantaneous: 3 NO + 1 HL EC delayed: 0 SC: 0 Autostart/monitored start Basic device Maximum achieved SIL: 3, PL: e

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3TK2853-1BB40 key specifications
ParameterValue
Type of electrical connectionscrew-type terminals
Safety device type according to IEC 61508-2Type B
Type of electrical connection Plug-In socketYes
Type of voltage of the control supply voltageDC
Type of the Safety-Related wiring of the inputssingle-channel and two-channel
Insulation voltage rated value690 V
Surge voltage resistance rated value6 000 V
Design of the fuse link for short-circuit protection of the NO contacts of the relay outputs requiredgL/gG: 10 A
Recovery time after power failure typical7 s
Operating frequency maximum1 000 1/h
Protection class IP of the enclosureIP20
Mounting positionany
3TK2853-1BB40 — By operating voltage
ParameterValue
At 24 V10 A
At 115 V6 A
At 230 V6 A

All specifications

3TK2853-1BB40 additional specifications
ParameterValue
Installation environment regarding EMCThis product is suitable for Class A environments only. In household environments, this device can cause unwanted radio interference. The user is required to implement appropriate measures in this case.
Installation altitude at height above sea level maximum2 000 m
DC resistance of the cable maximum500 Ω
Protection class IP of the terminalIP20
Shock resistance5g / 11 ms
EMC emitted interferenceIEC 60947-5-1, IEC 60000-4-3, IEC 60000-4-5, IEC 60000-4-6
Relative humidity during operation10 ... 95 %
Touch protection against electrical shockfinger-safe
Vibration resistance according to IEC 60068-2-65 ... 500 Hz: 0,075 mm
Depth108 mm
Width90 mm
Height132 mm
UL approvalYes
BG BIA approvalYes
According to IEC 615083
Hardware fault tolerance according to IEC 615081
Solid2x (24 ... 18)
At DC0.85 ... 1.1
Typical120 ms
Stranded2x (24 ... 18)
Start inputYes
Safety switchYes
At DC maximum100 ms
During storage-40 ... +80 °C
Feedback inputYes
Automatic startYes
During operation-25 ... +60 °C
Mountingscrew and snap-on mounting
Valve monitoringNo
Delayed switching0
At DC rated value24 V
Monitored Start-UpYes
Contact reliabilityone incorrect switching operation of 100 million switching operations (17 V, 5 mA)
Design of the productfor EMERGENCY-STOP and safety doors
Instantaneous contact0
Standstill monitoringNo
1-Channel or 2-Channel1
EMERGENCY OFF functionYes
Light array monitoringYes
Design of the cascadingcascading and in-service switching
Safety-Related circuitsYes
Laser scanner monitoringYes
Light barrier monitoringYes
With core end processing1x (0.25 ... 2.5 mm²), 2x (0.25 ... 1.0 mm²)
Rotation speed monitoringNo
Tactile sensor monitoringYes
Position switch monitoringYes
Protective door monitoringYes
Of the sensor input minimum45 ms
Monitoring of floating sensorsYes
Of the cascading input minimum0.045 s
EMERGENCY-OFF circuit monitoringYes
Safety-Related delayed switching0
Pressure-Sensitive mat monitoringYes
Monitoring of Non-Floating sensorsYes
Air pressure according to SN 3120590 ... 106 kPa
Of the ON pushbutton input minimum0.2 s
Product feature Cross-Circuit-ProofYes
Cascading input (Functional switching)Yes
Safety-Related instantaneous contact3
Category according to EN ISO 13849-14
Stop category according to EN 60204-10
Reference code according to EN 61346-2F
Magnetically operated switch monitoringNo
Contact reliability of auxiliary contacts< 1 error per 100 million operating cycles
Suitability for interaction press controlYes
For signaling function instantaneous contact0
Magnetically operated switch monitoring NC-NCYes
Magnetically operated switch monitoring NC-NONo
PFHD with high demand rate according to EN 620611.1E-8 1/h
SIL claim limit (subsystem) according to EN 620613
Mechanical service life (Operating cycles) typical30 000 000
Recovery time after opening of the safety circuits typical500 ms
Backslide delay time after opening of the safety circuits typical50 ms
MPN