3UG3014-1BR60 — Identification
ParameterValue
Product functionActive power monitoring relay
Product line / brand nameSIRIUS
3UG3014-1BR60 — Electrical
ParameterValue
Rated value (50 Hz)410 ... 550 V
Rated value (60 Hz)410 ... 550 V
3UG3014-1BR60 — Communication
ParameterValue
Electrical connection typescrew-type terminals
3UG3014-1BR60 — Environmental
ParameterValue
Ingress protection (IP rating), wiredIP20
3UG3014-1BR60 — Mechanical
ParameterValue
Mounting typesnap-on mounting
Width45 mm
Height100 mm
Depth100 mm
Conductor cross-section, solid20 ... 14
Conductor cross-section, finely stranded (with ferrule)0.5 ... 2.5 mm²
Mounting clearance, top0 mm
Mounting clearance, rear0 mm
Mounting clearance, side0 mm
Mounting clearance, front0 mm

Product details

The Siemens 3UG3014-1BR60 is a SIRIUS active power monitoring relay — it watches real power (kW) on a motor or load and trips an alarm or shutdown when the power strays outside a set window, upper or lower limit. Rated for 410-550 VAC at 50/60 Hz, it measures load current from 0.2 to 10 A via an external current transformer (not included). The relay output switches up to 3 A at 250/400 VAC, AC-15 rated for 100,000 operations at 230 V — enough for a contactor coil or PLC input.

Screw-type terminals accept 2 x 20-14 AWG solid or stranded. Torque to 1.2-0.8 N·m. IP20 protected; keep it inside the enclosure, not on the machine frame.

Setting the trip window and timing

Two adjustable delays: a start-up override (0.3-3 s) to ignore inrush, and a response delay on limit violation (0.5-20 s) to ride through short transients. Repeat accuracy is 1% of the set value; metering precision is 10% — adequate for overload or no-load detection, not for revenue-grade power logging.

Environmental and surge withstand

Vibration tested per IEC 60068-2-6: 15 mm at 1-6 Hz, 2g at 6-500 Hz. Shock: 15g / 11 ms half-sine. Surge voltage resistance rated at 6 kV — suitable for industrial environments with moderate transient exposure.

Frequently asked questions

What are the key ratings for this relay?

Supply voltage 410-550 VAC 50/60 Hz, measurable current 0.2-10 A via external CT, relay contacts rated 3 A at 250/400 VAC, IP20, snap-on DIN rail mount, 45 mm wide.