Siemens 3UG4614-2BR20 — Process / Temperature Controllers

Siemens SIRIUS 3UG4614-2BR20 Network Monitoring Relay, 160-6

MPN3UG4614-2BR20
NRND

Siemens SIRIUS network monitoring relay, 3UG4614-2BR20, 160-690 V AC 50/60 Hz, 3 A switching, LCD display, snap-on 22.5 mm housing.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3UG4614-2BR20 — Identification
ParameterValue
Product functionPhase monitoring relay
Product designationNetwork monitoring relay with digital setting
Product line / brand nameSIRIUS
3UG4614-2BR20 — Electrical
ParameterValue
Rated value (50 Hz)160 ... 690 V
Rated value (60 Hz)160 ... 690 V
3UG4614-2BR20 — Communication
ParameterValue
Electrical connection typespring-loaded terminals
3UG4614-2BR20 — Environmental
ParameterValue
Ingress protection (IP rating), wiredIP20
Installation altitude, max.2 000 m
3UG4614-2BR20 — Mechanical
ParameterValue
Fastening methodsnap-on mounting
Mounting positionany
Width22.5 mm
Height94 mm
Depth91 mm
Conductor cross-section, solid24 ... 16
Conductor cross-section, finely stranded (with ferrule)0.25 ... 1.5 mm²
Mounting clearance, top0 mm
Mounting clearance, rear0 mm
Mounting clearance, side0 mm
Mounting clearance, front0 mm

Product details

The Siemens SIRIUS 3UG4614-2BR20 is a network monitoring relay with digital setting, designed to monitor AC phase parameters in three-phase systems. It covers a rated voltage range of 160 to 690 V AC at both 50 and 60 Hz, making it suitable for standard industrial mains across most regions. The relay detects phase asymmetry and includes an auto-reset function, with a configurable start-up delay from 0.1 to 20 s to ride through momentary dips. Switching capacity is rated at 3 A at 250 V and 400 V AC (50/60 Hz), with lower ratings for DC loads: 1 A at 24 V, 0.2 A at 125 V, and 0.1 A at 250 V. The output relay provides a changeover contact, and isolation between outputs is confirmed. Clearance around the device is 0 mm in all directions, meaning it can be packed tightly against other components without derating. The front panel includes an LCD display for parameter readout, but no LED bar graph.

Wiring & Termination

The screw-type clamps are sized for standard control wiring; strip length and torque follow Siemens recommendations. The relay's output is a single changeover contact rated for general-purpose AC loads; for DC switching, derate per the listed values.

Frequently asked questions

What are the key ratings of the 3UG4614-2BR20?

It monitors AC voltage from 160 to 690 V at 50/60 Hz. The output relay switches 3 A at 250/400 V AC, or 1 A at 24 V DC. It detects phase asymmetry and has an auto-reset function with a 0.1-20 s start delay.

What is the physical size and mounting of the 3UG4614-2BR20?

It is 22.5 mm wide, 94 mm high, and 91 mm deep. It snaps onto a DIN rail and can be mounted in any position with zero clearance required on all sides.

What wire sizes does the 3UG4614-2BR20 accept?

It accepts solid or stranded wire from 24 to 16 AWG, and up to 2x 24-16 AWG solid conductors per terminal.