Skip to main content
Siemens 3UG5625-1CW30 — Process / Temperature Controllers

Siemens 3UG5625-1CW30 Residual Current Monitoring Relay, 0.0

MPN3UG5625-1CW30
Active

Siemens 3UG5625-1CW30, Residual current monitoring relays, digital monitoring relay, adjustment range 0.03...40 A, supply voltage 24...240 V AC/DC, 2 changeover contacts, screw terminal.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3UG5625-1CW30 — Identification
ParameterValue
Product familyResidual current monitoring relays
3UG5625-1CW30 — Approvals
ParameterValue
RoHS complianceSince: 01-06-23
REACH Art. 33 (SVHC disclosure)Lead CAS-No. 7439-92-1 > 0,1 % (w / w)
3UG5625-1CW30 — Other specifications
ParameterValue
Group codeR711
Product group5885
Product classA: Standard product which is a stock item could be returned within the returns guidelines/period.
Export control regulationsAL : N / ECCN : 9N9999

Product details

The Siemens 3UG5625-1CW30 is a digital monitoring relay for residual current, part of the Residual current monitoring relays family. It requires an external current transformer (3UL23) and covers an adjustment range of 0.03 to 40 A, with a supply voltage of 24 to 240 V AC/DC at 50/60 Hz. On-delay and tripping delay are independently settable from 0.1 to 999.9 seconds, and the output is two changeover contacts on screw terminals.

The 0.03 to 40 A adjustment range means this relay can monitor leakage from a few milliamps (sensitive for personnel protection) up to 40 A (equipment ground-fault levels on larger feeders). The wide supply voltage — 24 to 240 V AC/DC — lets it run on control power or line voltage without a separate power supply module. The 0.1 to 999.9 s timing range covers both fast tripping (for shock protection) and delayed trip (to ride through inrush or transient leakage). Two changeover contacts give one N/O and one N/C per contact, enough to signal a fault and latch a shunt trip in the same device.

RoHS compliant since 01-06-23. Export Control Regulations: AL N / ECCN 9N9999.

Frequently asked questions

What are the key ratings of the 3UG5625-1CW30?

Adjustment range 0.03 to 40 A, supply voltage 24 to 240 V AC/DC, on-delay and tripping delay 0.1 to 999.9 s, two changeover contacts on screw terminals. Requires external current transformer 3UL23.

What compliance documentation is available for the 3UG5625-1CW30?

RoHS compliant since 01-06-23. REACH Article 33 duty to inform applies due to lead content above 0.1% w/w. Export Control: AL N / ECCN 9N9999.

MPN
3UG5625-1CW30