Skip to main content
Siemens 3VA1010-2ED32-0AC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1010-2ED32-0AC0 SENTRON MCCB, 100 A, 52.5 kA

MPN3VA1010-2ED32-0AC0

Siemens SENTRON 3VA1010-2ED32-0AC0, molded case circuit breaker, 3-pole, 100 A (Iu), TM210 thermal-magnetic trip, 52.5 kA breaking at 240 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA1010-2ED32-0AC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA10102ED320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1010-2ED32-0AC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96 A
Current at 60 °C94 A
Current at 65 °C92 A
Current at 70 °C90 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA
3VA1010-2ED32-0AC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA1010-2ED32-0AC0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1010-2ED32-0AC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2
3VA1010-2ED32-0AC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1010-2ED32-0AC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

100 A MCCB with TM210 trip — line protection duty

The Siemens SENTRON 3VA1010-2ED32-0AC0 is a 3-pole molded case circuit breaker rated 100 A continuous at 40 °C (Iu = 100 A), with a TM210 thermal-magnetic trip unit for line protection. Its breaking capacity reaches 52.5 kA at 240 V AC, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V — figures that determine the available fault current it can safely interrupt at your service voltage.

The 100 A rating holds flat through 50 °C (–), then derates to 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C (–).

Frequently asked questions

Who supplies 3VA1010-2ED32-0AC0 and how is it quoted for volume purchases?

This part is sourced through independent distribution channels and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — no stock count or price figure is published here.

When sourcing 3VA1010-2ED32-0AC0, what's the closest functional second-source — 3VA1010-2ED32-0JA0?

The 3VA1010-2ED32-0JA0 is a peer variant in the same SENTRON 3VA1 frame. Both carry a 100 A TM210 trip and the same breaking capacities. The -0JA0 suffix adds a different auxiliary contact configuration — verify your control wiring before substituting. Same part, different passport; the dimensions and mounting footprint are identical, so it drops into the same panel without rewiring the power circuit.

What is 3VA1010-2ED32-0AC0's listed depth (70 mm) on this component line?

The depth is 70 mm. Combined with a width of 76.2 mm and height of 130 mm (–), it fits standard SENTRON panel cutouts and DIN-rail adapters.

Will 3VA1010-2ED32-0AC0 drop into a panel that was specified around 3VA1010-2ED32-0JA0 without rewiring?

Yes — both variants share the same 70 × 76.2 × 130 mm case dimensions and 3-pole line-protection design. The power terminals and mounting footprint are identical. The only difference is the auxiliary contact configuration; verify that the -0AC0's two HQ auxiliary switches match your control scheme before swapping.

MPN
3VA1010-2ED32-0AC0