Breaking capacity runs 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at both 500 V and 690 V — so the interrupting rating you spec depends on your system voltage. Thermal derating is flat to 50 °C — still 100 A — then drops to 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C.
Footprint is 76.2 mm wide, 130 mm tall, 70 mm deep — a standard 3-pole MCCB envelope that fits most DIN-rail or panel-mount backplates without re-drilling. Undervoltage release is present; no voltage-trip or ground-fault monitoring on this variant.
What the TM210 release means
This is the standard fixed-release design for line protection — no electronic adjustment, no communication function, just reliable electromechanical trip.