Siemens 3VA1010-2ED32-0HC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1010-2ED32-0HC0 SENTRON MCCB, 100 A, 3-Pole, 52.5

MPN3VA1010-2ED32-0HC0

Siemens SENTRON 3VA1010-2ED32-0HC0, 3-pole molded case circuit breaker, 100 A rated continuous current, 52.5 kA at 240 V, TM210 overcurrent release, shunt trip, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1010-2ED32-0HC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1010-2ED32-0HC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96 A
Current at 60 °C94 A
Current at 65 °C92 A
Current at 70 °C90 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA
3VA1010-2ED32-0HC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1010-2ED32-0HC0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1010-2ED32-0HC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2
3VA1010-2ED32-0HC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1010-2ED32-0HC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1010-2ED32-0HC0 is a 3-pole molded case circuit breaker rated for 100 A continuous current at 40 °C through 50 °C, with a TM210 thermal-magnetic overcurrent release and an integrated shunt trip (STL). It's a line-protection device — meaning it sits upstream of branch feeders or individual loads, not on a motor circuit. The interrupting ratings climb to 52.5 kA at 240 V and 32 kA at 415 V, which covers most industrial service-entrance and distribution panel fault levels.

Above that it derates stepwise: 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C.

Auxiliary contacts and shunt trip included

The auxiliary switches report position back to a PLC or status lamp.

Frequently asked questions

Where can I buy 3VA1010-2ED32-0HC0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the interrupting ratings for this MCCB?

52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V.

What is the rated continuous current and how does it derate with temperature?

100 A from 40 °C to 50 °C, then 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C.

MPN
3VA1010-2ED32-0HC0