Skip to main content
Siemens 3VA1010-2ED32-0JA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1010-2ED32-0JA0 SENTRON MCCB, 100 A, 3-Pole, Line

MPN3VA1010-2ED32-0JA0

Siemens SENTRON 3VA1010-2ED32-0JA0, molded case circuit breaker, 3-pole, 100 A, line protection, TM210 thermal-magnetic release, 52.5 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1010-2ED32-0JA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1010-2ED32-0JA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96 A
Current at 60 °C94 A
Current at 65 °C92 A
Current at 70 °C90 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA
3VA1010-2ED32-0JA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1010-2ED32-0JA0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1010-2ED32-0JA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA1010-2ED32-0JA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1010-2ED32-0JA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1010-2ED32-0JA0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current at 40 °C — that's the full rating up to 50 °C, then it derates to 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C. For a panel that runs warm, the 100 A frame still holds up in a 50 °C ambient without derating, which is where many breakers start to lose headroom. The interrupting ratings are 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V — so at 415 V it handles a 32 kA fault, which covers most industrial distribution panels fed from a 1 MVA transformer.

Mounts in a standard distribution panel or motor control center; the 76.2 mm width (3-pole frame) and 70 mm depth fit the SENTRON 3VA family footprint. The shunt trip (STL) auxiliary release is built in, so you can remotely trip the breaker from an emergency-stop circuit or a PLC output without adding an external undervoltage coil. No auxiliary contact version means you'll need a separate 3VA9688-0BL32 auxiliary trip block if you want a status feedback signal back to the controller.

Frequently asked questions

Where can I buy 3VA1010-2ED32-0JA0?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What are the key ratings for 3VA1010-2ED32-0JA0?

Rated continuous current 100 A, 3-pole, interrupting 52.5 kA at 240 V / 32 kA at 415 V / 13.6 kA at 440 V / 7.5 kA at 690 V, TM210 thermal-magnetic release, shunt trip, IP40 front.

Will 3VA1010-2ED32-0JA0 drop into a panel built for 3VA1010-2ED42-0AE0?

Yes — both are 3-pole, 100 A frame, same 76.2 mm width and 70 mm depth. The difference is the interrupting rating: the 2ED42-0AE0 carries a higher kA rating at certain voltages. If the panel's fault current is within the 2ED32-0JA0's ratings, it's a direct mechanical fit.

MPN
3VA1010-2ED32-0JA0