Breaking capacity is 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V — enough for most industrial service-entrance and feeder applications where fault current runs high.
The 100 A rating holds steady from 40 °C through 50 °C ambient; it derates to 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C.
The integrated auxiliary trip is order code 3VA9608-0BB24.