Skip to main content
Siemens 3VA1010-2ED36-0DH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1010-2ED36-0DH0 SENTRON MCCB, 100 A, 52.5 kA at 2

MPN3VA1010-2ED36-0DH0

Siemens SENTRON 3VA1010-2ED36-0DH0, molded case circuit breaker, 3-pole, 100 A at 40 °C, breaking capacity 52.5 kA at 240 V, line protection, undervoltage release, 2 aux + 1 trip alarm switch.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1010-2ED36-0DH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10102ED360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1010-2ED36-0DH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.27.5 W
3VA1010-2ED36-0DH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1010-2ED36-0DH0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1010-2ED36-0DH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3
3VA1010-2ED36-0DH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1010-2ED36-0DH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1010-2ED36-0DH0 is a 3-pole molded case circuit breaker (MCCB) rated 100 A at 40 °C, designed for line protection in distribution panels. Its breaking capacity reaches 52.5 kA at 240 V, tapering to 7.5 kA at 690 V — figures that govern fault-clearing capability across common low-voltage systems.

The 100 A rating holds continuously at 40 °C ambient; derate to 91 A at 70 °C if the panel runs hot. The 52.5 kA at 240 V is the maximum fault current the breaker can safely interrupt — downstream equipment must be coordinated so the available fault current stays under this threshold.

Dimensions: 130 mm height, 76.2 mm width, 70 mm depth — fits standard SENTRON mounting footprints. The 3-pole design with integral undervoltage release and auxiliary switch configuration (2 aux + 1 trip alarm HQ) means it can be wired directly into existing control circuits without external add-on modules.

Frequently asked questions

What is the breaking capacity of 3VA1010-2ED36-0DH0 at 240 V?

52.5 kA at 240 V, with lower values at higher voltages: 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 500 V and 690 V.

Where can I buy 3VA1010-2ED36-0DH0?

This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

MPN